Programming

53688

6-7

6.6.1.8 Walk Test Reporting

The default configuration for this option is No. If set to Yes, the panel generates a TEST report
to the central station when the walk test begins. During a walk test, the panel’s normal fire
alarm function is completely disabled, placing the panel in a local trouble condition. All zones
respond as 1-Count zones (respond when a single detector is in alarm) during a walk test.
Each alarm initiated during the walk test will be reported.

6.6.1.9 Walk Test duration

Enter the amount of time, in minutes, for the walk test duration. When the programmed
amount of time expires, the Walk Test will end automatically.

6.6.1.10 Walk Test NAC Time out

Enter the amount of time, in seconds, for the walk test NAC active duration. During a walk
test alarm activation, the NACs will automatically deactivate after the programmed amount of
time expires.

6.6.1.11 Clock Source

The panel’s AC line frequency is selectable for 60 Hz, 50 Hz, or Internal Clock Source. AC
frequency feature dictates how the control panel will calculate time based on the AC line
frequency used in the installation site. The “Internal Clock” option can be used in areas where
the AC line frequency is not dependable and you want the panel to calculate time from the
internal crystal. The internal crystal is not as accurate as the AC power source. The panel
defaults to the 60 HZ selection.

6.6.1.12 Auto Daylight Savings Time

Select this feature to “Yes” if you want the panel to automatically adjust the clock to track
with daylight savings time.

6.6.1.13 Remote Annunciator

Select this feature to “Yes” if a ANN-80 Remote Annunciator is to be used. A customized
banner can also be added to the Remote Annunciator. The Remote Annunciator allows for the
top 2 lines to be programmed as a custom banner.