1 current draw worksheet for ms-25 ul 864, 1 current draw worksheet for ms-25 ul 864 -6 – Fire-Lite MS-25E Addressable Fire Control Panel User Manual

Page 26

Advertising
background image

Model MS-25 Installation and Operation Manual

3-6

53688

3.6.1.1 Current Draw Worksheet for MS-25 UL 864

Use Table 3-2 to determine amp-hour requirements during alarm/battery standby operation.
(Copy the page if additional space is required.) You can install up to 25 SLC devices and two
ANN-80 Remote Annunciator.

Table 3-2: Current Calculation Worksheet for SLC Devices

Device

# of Devices

Current per Device

Standby

Current

Alarm

Current

For each device use this formula: This column X This column = Current per number of devices.

Fire Panel (Current draw from
battery)

1

Standby: 135 mA

135 mA

Alarm: 220 mA

220 mA

Accessory Modules

ANN-80 Remote Annunicator

2

Standby: 37 mA mA

Alarm: 40 mA

mA

Addressable SLC Detectors

HFS-P

(25 max.

detectors or

modules in any

combination)

Standby: 0.27 mA

Alarm: 6.5 mA

mA

mA

HFS-PT

mA

mA

HFS-D

mA

mA

HFS-T

mA

mA

SD355

mA

mA

SD355T

mA

mA

D355PL

mA

mA

H355

mA

mA

Addressable SLC Modules

HFS-MM

(25 max.

detectors or

modules in any

combination)

Standby/Alarm: 0.375 mA

mA

mA

BG-12LX

Standby/Alarm: 0.375 mA

mA

mA

HFS-MR

Standby/Alarm: 0.255mA

mA

mA

MMF-301

Standby/Alarm: 0.375 mA

mA

mA

CRF-300

Standby/Alarm: 0.375 mA

mA

mA

I300

10 max.

Standby/Alarm: 0.45 mA

mA

mA

A

Total System Current

Auxiliary Devices

Refer to devices manual for current rating.

Alarm/Standby: mA

mA

mA

Alarm/Standby: mA

mA

mA

Alarm/Standby: mA

mA

mA

B

Auxiliary Devices Current

Notification Appliance Circuits

Refer to device manual for current rating.

Alarm: mA

mA

Alarm: mA

mA

Alarm: mA

mA

Alarm: mA

mA

C

Notification Appliances Current

mA

D

Total current ratings of all devices in system (line A + line B + C)

mA

mA

E

Total current ratings converted to amperes (line D x .001):

A

A

F

Number of standby hours (24 or 60 for NFPA 72, chapter 1, 1-5.2.5):

H

G

Multiply lines E and F.

Total standby AH

AH