Caution – HT instruments PVCHECK User Manual

Page 21

Advertising
background image

PVCHECK

EN - 19

modules’ Voc.
Manual

 setting, made by the operator, of the known

temperature value of the module in the line below.
Aux

 temperature measurement with auxiliary probe

PT1000.

Tol. Voc (%)  percentage value of the desired limit

tolerance (set by the operator according to his/her own
requirements) for the measurement of Voc carried out
by the instrument. Allowable values: 0%

25%. The

value between brackets (4%) indicates the reading
error of the instrument in Voc measurement.

Tol. Isc (%)  percentage value of the desired limit

tolerance (set by the operator according to his/her own
requirements) for the measurement of Isc carried out
by the instrument. Allowable values: 0%

25%. The

value between brackets (4%) indicates the reading
error of the instrument in Isc measurement.

Ins Test  enabling/disabling of insulation

measurement and setting of test voltage. Possible
options: OFF, 250V, 500V, 1000V. With enabled
function, the line “Ri min” appears, which allows
setting the minimum limit threshold in the range 0.1

100M

RPE Test  enabling/disabling of continuity test and

setting of the limit threshold value for measurement.
Possible options OFF, 1

5 in steps of 1

5. Press the SAVE key to save the settings made; the

message “Data saved” will be displayed for a few
seconds. Press the ESC/MENU key to exit without saving
and go back to the previous screen.

CAUTION

The settings saved for test voltage for the insulation measurement carried out
within the IVCK function also affect the settings for the single measurement
(MENU

M

).