Pvcheck, Measuring… selection m, Outcome: ok m – HT instruments PVCHECK User Manual

Page 44

Advertising
background image

PVCHECK

EN - 42

4. Press GO/STOP to start the test. In case no error

conditions occur, the instrument displays the message
Measuring…” as shown in the screen to the side.

15/05/12 15:34:26

I n s . T e s t

:

1 0 0 0

V

R i m i n

:

1 . 0

M

M o d e :

T i m e r

V t e s t

1 0 2 0

V

R i ( + ) m i n

- - -

M

T e s t t i m e : 1 0 s

Measuring…

Selection

M

5. When measurement is complete, the instrument provides

the Ri(+)min value, i.e. the minimum value of insulation
resistance of the PV module/string (or of other metal
masses) being tested, continuously measured during the
whole duration of measurement. If the result is higher
than the minimum limit set, the instrument displays the
message “Outcome:OK”; otherwise, it displays the
message “Outcome:NO” as shown in the screen to the
side.

6. Press the SAVE key to store the test result in the

instrument’s memory (see § 7.2) or the ESC/MENU key
to exit the screen without saving and go back to the main
measuring screen.


























15/05/12 15:34:26

I n s . T e s t

:

1 0 0 0

V

R i m i n

:

1 . 0

M

M o d e :

T i m e r

V t e s t =

1 0 2 0

V

R i ( + ) m i n =

> 2 0 0

M

T e s t t i m e : 2 0 0 s

Outcome: OK

M