KYORITSU 6050 User Manual

Page 13

Advertising
background image

̶ 11 ̶

● Reference

  conditions

Specifications are based on the following

conditions except where otherwise stated.

 1. Ambient temperature : 23±5℃

 2. Relative humidity : 45% to 75%

 3. Position : horizontal

 4. AC power source : 230V,50Hz

 5. Altitude : Up to 2000m

● Operating

  temperature and

  humidity.

0 to 40℃ , relative humidity 85% or less, no

condensation.

● Storage

  temperature and

  humidity.

-20 to +60℃ , relative humidity 85% or less, no

condensation.

● Symbols used on

the instrument

Equipment protected throughout by

DOUBLE INSULATION or REINFORCED

INSULATION.

#

Caution (refer to accompanying instruction

manual)

● Battery type

Eight R6 or LR6 batteries

Measurement times : approx 800 times or

more. (Measure at the interval of 30 sec on DC

10mA range of RCD function.)

● Operating Errors of Loop impedance (IEC 61557-3)

The influencing variations used for calculating the operating error are

denoted as follows:

Temperature : 0℃ and 40℃

Phase angle : At a phase 0°to 18°

System frequency : 49.5Hz to 50.5Hz

System voltage : 230V+10%-15%

Supply voltage : 8V to 13.8V

Range
20Ω
200Ω
2000Ω

Measuring range to keep
operating error
 0.4 ∼19.99Ω
 20.0∼199.9Ω
 200 ∼1999Ω

Maximum percentage
operating error

±30%