Loop impedance / psc tests – KYORITSU 6050 User Manual

Page 15

Advertising
background image

̶ 13 ̶

5.1 Principles of Measurement

5.1-1 Measurement of Fault Loop Impedance and Prospective Fault

Current

If an electrical installation is protected by over- current protective devices

including circuit breakers or fuses, the earth fault loop impedance should be

measured.

In the event of a fault the earth fault loop impedance should be low enough

(and the prospective fault current high enough)to allow automatic

disconnection of the electrical supply by the circuit protection device within a

prescribed time interval.

Every circuit must be tested to ensure that the earth fault loop impedance

value does not exceed that specified or appropriate for the over- current

protective device installed in the circuit.

For a TT system the earth fault loop impedance is the sum of the following

impedances;

● Impedance of the power transformer secondary winding.

● Impedance of the phase conductor resistance from the power transformer

to the location of the fault.

● The impedance of the protective conductor from the fault location to the

local earth system.

● Resistance of the local earth system (R).

● Resistance of the power transformer earth system (Ro).

 5. LOOP IMPEDANCE / PSC TESTS

Fig.9

Advertising