Typical examples of instrument connection
Practical example of 3-phase + neutral RCD test in a TT system.
Practical example of 3-phase + neutral RCD test in a TN system
General(G)
300ms
max. allowed Value
500ms
max. allowed Value
130ms
min. allowed Value
40ms
max. allowed Value
150ms
max. allowed Value
50ms
min. allowed Value
Type of RCD
I⊿n
5I⊿n
Selective(S)
Fig.16
Fig.17