For the RCD range of Model 6050, distortion factor of test current

is improved compared with our traditional instruments. Therefore,

at operating time measurement of RCD, operating time of some

RCD and our traditional instruments may differ a little.

 7. Uc TESTS

● The earth electrode resistance of a measuring circuit with a probe

shall not exceed table1(page 12).

7.1 Principles of Measurement

In fig.16, when grounding is incomplete and R exists, voltage occurs to

R if fault current flows in R. Person may touch this voltage, and the

voltage occurs to a person at this bout is called as Uc. At Uc test, the

value, when Uc reaches maximum, is calculated.

7.2 Uc Testing

7.2.1 Preparation

(1) Turn Function switch and power on the instrument. Select Uc.

(2) Press the "I⊿n / LOOP / PSC" SELECT SWITCH to set the Rated

Tripping Current (I⊿n) to the rated trip current of the RCD. Every

time "I⊿n / LOOP / PSC" SELECT SWITCH is pressed, ▼mark on

LCD shifts. Select I⊿n with above switch.

7.2.2 Wiring Check

(1) Insert the Test Lead into the instrument.(Fig.15)

(2) Connect test lead to object to be tested.(Fig.16,17)

(3) Make sure that the P-E and P-N wiring Check LEDs are lit and the

wiring in correct LED is not lit. If it is not correct, disconnect the

tester and check the wiring for a possible fault.

I⊿n

30mA

The Initial value