For TN systems the earth fault loop impedance is the sum of the following

impedances.

● Impedance of the power transformer secondary winding.

● Impedance of the phase conductor from the power transformer to the

location of the fault.

● Impedance of the protective conductor from the fault location to the power

transformer.

In accordance with the international standard IEC 60364 for a TT system the

following condition shall be fulfilled for each circuit.

RA must be <_50/la

where;

RA is the sum of the resistances of the local earth system R and the

protective conductor connecting it to the exposed conductor part.

50V is the maximum voltage limit (it may be 25V in certain circumstances).

la is the value of current that causes automatic disconnection of the

protective device within 5 seconds.

When the protective device is a residual current device (RCD), Ia is the rated

residual operating current I⊿n.

For example in a TT system protected by an RCD the maximum RA values

are as follows;

Fig.10

Rated residual operating current I⊿n mA

10

5000
2500

30

1667

833

100
500
250

300
167

83

500
100

50

1000

50
25

RA (at 50V)Ω
RA (at 25V)Ω