KYORITSU 6050 User Manual

Page 14

Advertising
background image

̶ 12 ̶

Function

Operating error of trip current

Ч1/2

-10%∼0%

Ч1

0%∼+10%

Ч5

0%∼+10%

Auto Ramp

-10%∼+10%

● Operating Errors of trip current (IEC 61557-6)

The influencing variations used for calculating the operating error are

denoted as follows:

Temperature : 0℃ and 40℃

Earth electrode resistance :

I n(mA)

10
30

100
300
500

1000

Earth electrode resistance(Ω)

UL50V

2000

600
200
130

80
40

UL25V

2000

600
200

65
40
20

table.1

System voltage : 230V+10%-15%

Supply voltage : 8V to 13.8V

#

CAUTION

Even though the test current in the 2000 ohm range (15mA test

current) is low some RCD's may trip due to sensitivity or where

there may already be additional leakage in the circuit being tested.
The Loop impedance in a TN system is small and therefore it is

not recommended to test in the 2000 ohm range. RCD's will have

to be bridged to avoid tripping when using other test ranges.