Rcd tests – KYORITSU 6050 User Manual

Page 22

Advertising
background image

̶ 20 ̶

6.1 Principles of Measurement

The RCD tester is connected between phase and protective connectors

on the load side of the RCD after disconnecting the load. A precisely

measured current for a carefully timed period is drawn from the phase

and returns via the earth, thus tripping the device. The instrument

measures and displays the exact time taken for the circuit to be opened.

An RCD is a switching device designed for breaking currents when the

residual current attains a specific value. It works on the basis of current

difference between phase currents flowing to different loads and

returning current flowing through the neutral conductor (for a single-

phase installation). In the case where the current difference is higher

than the RCD tripping current, the device will trip and disconnect the

supply from the current.

There are two classifications for RCDs; the first one due to the shape of

the residual current wave form (types AC and A)and the second due to

the tripping time (types G and S).

● RCD type AC will trip when presented with residual sinusoidal

alternating currents whether applied suddenly or slowly rising. This

type is the most frequently used on electrical installations.

● RCD type A will trip when presented with residual sinusoidal

alternating currents (similar to type AC)and residual pulsating direct

currents (DC)whether suddenly applied or slowly rising. This type of

RCD is not commonly used at present, however, it is increasing in

popularity and is required by the local regulations in some countries.

● RCD type G. In this case G stands for general type (without trip- out

time delay)and is for general use and applications.

● RCD type S where S stands for selective type (with trip-out time

delay).This type of RCD is specifically designed for installations

where the selectivity characteristic is required. In order to assure

successful protection on an electrical installation using RCD's they

should be checked to test trip- out time t⊿.

● Trip- out time t⊿ is the time needed by the RCD to trip at a rated

residual operating current of I⊿n. The standard values of tripping

time are defined by IEC 61009 (EN61009) and IEC 61008 (EN

61008) and are listed in the table below for I⊿n and 5I⊿n.

 6. RCD TESTS

Advertising