̶ 22 ̶

6.2 RCD Testing

6.2.1 Preparation

(1) Turn Function switch and power on the instrument. Select RCD.

(2) Press RCD Function switch to select RCD Function for test.

Selected function will be displayed on LCD.

(3) Press the "I⊿n / LOOP / PSC" SELECT SWITCH to set the Rated

Tripping Current (I⊿n) to the rated trip current of the RCD. Every

time "I⊿n / LOOP / PSC" SELECT SWITCH is pressed, ▼ mark on

LCD shifts. Select I⊿n with above switch.

(4) Press the UL value select switch to select switch UL value (25 or

50V).

6.2.2 Wiring Check

(1) Insert the Test Lead into the instrument. (Fig.15)

(2) Connect test lead to object to be tested. (Fig.16,17)

(3) Make sure that the P-E and P-N wiring Check LEDs are lit and the

wiring in correct LED is not lit. If it is not correct, disconnect the

tester and check the wiring for a possible fault.

For testing RCD's to verify that
they are not too sensitive.
For measuring the trip time.
For testing at I⊿n ×5.
For testing DC sensitive RCD's.
For measuring the trip out current.

Ч 1/2

Ч 1
Ч 5

DC

AUTO RAMP TEST(

)

RCD Function

I⊿n

0°/180°

UL

× 1/2

30mA

50V

The Initial value