5.2.2 Wiring Check

(1) Insert the Test Lead into the instrument.(Fig.15)

(2) Connect test lead to object to be tested.(Fig.11,12,13,14)

(3) Make sure that the P-E and P-N wiring Check LEDs are lit and the

wiring in correct LED is not lit. If it is not correct, disconnect the

tester and check the wiring for a possible fault.

5.2.3 Testing

(1) Press the test button. A beep will sound as the test is conducted and

the value of loop impedance will be displayed.

Note: When Test Lead removed during a measurement, "no" is

displayed on LCD and a measurement will be stopped. Please

check Test Lead is rightly connected.

● LOOP range

● PSC range

LOOP Range

PSC Range

2000Ω

200A

The Initial value

#

CAUTION

The RCD of a circuit shall be bypassed when measuring on LOOP 20

Ω range. Do not operate the Test button on RCD while RCD is

bypassed. Be sure to get back the bypassed RCD after test.