Practical example of verification of the protection is a TT system

according to the international Standard IEC 60364.

Fig.12

The maximum value of Zs for this example is 2.1Ω(16amp gG fuse,0.4

seconds).The loop tester reads 1.14Ωand consequently the condition

Zs<_Uo / la is met.

5.1.2 Principles of the Measurement of Line Impedance and

Prospective Short Circuit Current

Line impedance is the impedance, which is measured between Phase-

terminal L and Neutral-terminal N of single-phase system, or between

two phases of three-phase system. Measurement principal used in this

instrument is the same as it for Fault loop impedance measurement, but

measurement is performed between Terminal L and N, or between two

phases.

Breaking current capacity of installed over-current protection devices

should be higher than Prospective Short-Circuit current, otherwise it is

necessary to change the rated current of involved over-current

protection device.