Componenti di controllo e sicurezza, Quadro elettrico di controllo e potenza, Control and safety components – Airedale EcoChill 6kW - 46kW User Manual

Page 10: Electrical control and power panel

Advertising
background image

10

EcoChill Installation Manual 7481930_v1.6.0_08_2013

ECL-ECLH 020-202

EN

Electronic controller

MODU CONTROL

Control of the leaving water temperature with a proportional-integral algorithm: main-

tains the average leaving temperature to the desired valve

− Auto-adaptive differential starter timer: ensures the compressor minimum required

running time for systems with low water content

− Intelligent defrost by decreasing pressure: determines when the coil is frosted avoid-

ing unnecessary defrost cycles

− External air temperature setpoint compensation (with external air temperature sensor

accessory): reduces electrical consumption

− Condensing control based on pressure, rather than temperature, for absolute stability

(with DCPX fan speed controller accessory)

− Inverted condensing control for operation in heat pump mode even in the summer

(with DCPX fan speed controller accessory)

− Pre-alarms with automatic reset: in case of alarms a number of restarts are permitted

before a definitive lock out

− Alarm based on ∆T: to identify errors (reverse rotation) or reversing valve blocked

− Compressor hour run counter

− Compressor number of starts counter

− Alarm history

− Automatic restart after power failure

− Local or remote control

Display of unit status:

1.

Power on

2.

Compressor ON/OFF

3.

Operating mode (heating/cooling)

4.

Alarm active

Display of sensors, transducers and parameters

1.

Water outlet temperature

2.

Water inlet temperature

3.

Coil temperature (heat pump unit)

4.

Discharge refrigerant temperature

5.

External air temperature (heat pump, cooling only with DCPX and sensor)

6.

Discharge pressure (heat pump unit)

7.

Suction pressure (heat pump unit)

8.

Error from setpoint temperature (sum of the proportional and integral error)

9.

Delay time to start / stop the compressor

10. Control of alarms

11. Low pressure

12. High pressure (pre-alarm: pressostat directly removes power to the compressor)

13. High discharge temperature

14. Anti-freeze

15. Flow protection

16. Alarm based on ∆T

− Alarms with automatic reset and limited number of resets before definitive lock out

− ON/OFF control from remote contact

− Change of season from remote contact

For further information refer to the user manual.

SAFETY VALVE

With discharge pipe connection facility, and will operate

in cases of hydraulic system overpressure.

AIR VENT

(Versions "P-N-A-Q")

Mounted at the highest level of the hydraulic system. The

air vent is used for the release of any air pockets from the

hydraulic circuit.

SYSTEM BUFFER TANK

Manufactured in steel and to reduce heat gain and avoid

the formation of condensation is insulated with polyure-

thane material of adequate thickness.

The buffer tank reduces the number of compressor starts

and stabilises the water temperature delivered to the

system.

5.5. CONTROL AND SAFETY COMPONENTS

HIGH PRESSURE PRESSOSTAT (manual reset)

Fixed setting, fitted on the refrigerant high pressure

side, stops the operation of the compressor in case of

abnormal pressures.

LOW PRESSURE PRESSOSTAT

(only versions "° | C")

Fixed setting, fitted on the refrigerant low pressure

side, stops the operation of the compressor in case of

abnormal pressures.

HIGH PRESSURE TRANSDUCER

Mounted on the refrigerant circuit high pressure side

provides the operating pressure to the control board and

generates a pre-alarm in case of abnormal pressure.

LOW PRESSURE TRANSDUCER

(only version "H")

Mounted on the refrigerant circuit low pressure side

provides the operating pressure to the control board and

generates a pre-alarm in case of abnormal pressure.

5.6. ELECTRICAL CONTROL AND POWER

PANEL

Electrical panel conforming to EN 60204-1/IEC 204-1,

complete with:

- Control circuit transformer

- Door interlocked isolator

- Circuit breakers and contactors for compressors and

fans

- Terminals for REMOTE PANEL

- Spring type terminals for control circuit

- Externally rated cabinet with double panel and seals

- Electronic controller

- Relay output for evaporator pump and heat recovery

pump enable (only for versions without pump assem-

bly)

- All cables numbered

DOOR INTERLOCKED ISOLATOR

Access to the electrical panel is by operating the handle

of the door interlocked isolator which removes power

to the unit. To avoid accidentally powering up the unit

during maintenance the isolator is fitted with a locking

mechanism.

CONTROLLER KEYPAD

Allows complete control of the unit. For further informa-

tion refer to the user manual