Tarature parametri di controllo e sicurezze, Control and safety parameter settings – Airedale EcoChill 6kW - 46kW User Manual

Page 58

Advertising
background image

58

EcoChill Installation Manual 7481930_v1.6.0_08_2013

ECL-ECLH 020-202

EN

18. CONTROL AND SAFETY PARAMETER SETTINGS

COOLING SETPOINT

min

max

default

Water inlet temperature (cooling mode)

-6 °C

18 °C

7° C

HEATING SETPOINT
Water inlet temperature (heating mode)

35 °C

55 °C

48 °C

ANTI-FREEZE ALARM SETTING
EVAPORATOR side temperature setting

-9 °C

4 °C

3 °C

TOTAL DIFFERENTIAL
Proportional temperature band within which compres-
sors are enabled and disabled

3 °C

10 °C

5 °C

020

025

030

040

050

070

080

090

102

152

202

VERSIONS COOLING ONLY

FAN CIRCUIT BREAKERS
MTV1

A

2

2

2

2

2

2

2

2

2

2

2

MTV2

A

-

-

-

-

2

2

2

2

2

2

2

COMPRESSOR CIRCUIT BREAKERS

MTC1

A

230V

16

16

20

25

-

-

-

-

-

-

-

A

400V/3N

2,2

2,2

6

8

10

13

15

16

10

12,5

15

MTC2

A

-

-

-

-

-

-

-

-

10

12,5

15

HIGH PRESSURE PRESSOSTAT
PA

bar

42

42

42

42

42

42

42

42

42

HIGH PRESSURE TRANSDUCER
TAP

bar

39

39

39

39

39

39

39

39

39

LOW PRESSURE TRANSDUCER
TBP

bar

4

4

4

4

4

4

4

4

4

VERSIONS HEAT PUMP

FAN CIRCUIT BREAKERS
MTV1

A

2

2

2

2

2

2

2

2

2

2

2

MTV2

A

-

-

-

-

2

2

2

2

2

2

2

COMPRESSOR CIRCUIT BREAKERS

MTC1

A

230V

16

16

20

25

-

-

-

-

-

-

-

A

400V/3N

2,2

2,2

6

8

10

13

15

16

10

12,5

15

MTC2

A

-

-

-

-

-

-

-

-

10

12,5

15

HIGH PRESSURE PRESSOSTAT
PA

bar

42

42

42

42

42

42

42

42

42

42

42

LOW PRESSURE PRESSOSTAT
PA

bar vers."°"

2

2

2

2

2

2

2

2

2

2

2

LOW PRESSURE TRANSDUCER
TAP

bar vers."°"

4

4

4

4

4

4

4

4

4

4

4

TAP

bar vers."H"

2

2

2

2

2

2

2

2

2

2

2

HIGH PRESSURE TRANSDUCER
TBP

bar

40

40

40

40

40

40

40

40

40

40

40