18. CONTROL AND SAFETY PARAMETER SETTINGS
COOLING SETPOINT
min
max
default
Water inlet temperature (cooling mode)
-6 °C
18 °C
7° C
HEATING SETPOINT
Water inlet temperature (heating mode)
35 °C
55 °C
48 °C
ANTI-FREEZE ALARM SETTING
EVAPORATOR side temperature setting
-9 °C
4 °C
3 °C
TOTAL DIFFERENTIAL
Proportional temperature band within which compres-
sors are enabled and disabled
3 °C
10 °C
5 °C
020
025
030
040
050
070
080
090
102
152
202
VERSIONS COOLING ONLY
FAN CIRCUIT BREAKERS
MTV1
A
2
2
2
2
2
2
2
2
2
2
2
MTV2
A
-
-
-
-
2
2
2
2
2
2
2
COMPRESSOR CIRCUIT BREAKERS
MTC1
A
230V
16
16
20
25
-
-
-
-
-
-
-
A
400V/3N
2,2
2,2
6
8
10
13
15
16
10
12,5
15
MTC2
A
-
-
-
-
-
-
-
-
10
12,5
15
HIGH PRESSURE PRESSOSTAT
PA
bar
42
42
42
42
42
42
42
42
42
HIGH PRESSURE TRANSDUCER
TAP
bar
39
39
39
39
39
39
39
39
39
LOW PRESSURE TRANSDUCER
TBP
bar
4
4
4
4
4
4
4
4
4
VERSIONS HEAT PUMP
FAN CIRCUIT BREAKERS
MTV1
A
2
2
2
2
2
2
2
2
2
2
2
MTV2
A
-
-
-
-
2
2
2
2
2
2
2
COMPRESSOR CIRCUIT BREAKERS
MTC1
A
230V
16
16
20
25
-
-
-
-
-
-
-
A
400V/3N
2,2
2,2
6
8
10
13
15
16
10
12,5
15
MTC2
A
-
-
-
-
-
-
-
-
10
12,5
15
HIGH PRESSURE PRESSOSTAT
PA
bar
42
42
42
42
42
42
42
42
42
42
42
LOW PRESSURE PRESSOSTAT
PA
bar vers."°"
2
2
2
2
2
2
2
2
2
2
2
LOW PRESSURE TRANSDUCER
TAP
bar vers."°"
4
4
4
4
4
4
4
4
4
4
4
TAP
bar vers."H"
2
2
2
2
2
2
2
2
2
2
2
HIGH PRESSURE TRANSDUCER
TBP
bar
40
40
40
40
40
40
40
40
40
40
40