27. OPERATING CHARACTERISTICS

27.1. COOLING SETPOINT

(Factory default) = 7°C, ∆t = 5 K.

27.2. HEATING SETPOINT

(Factory default) = 45°C, ∆t = 5 K.

In the event of a momentary power interruption the

selected operating mode will be retained in memory.

27.3. COMPRESSOR DELAY TIMERS

To avoid excessive compressor starts two functions are

provided:

- Minimum time from last stop 60 seconds in cooling

mode.

- Minimum time from last start 300 seconds in heat-

ing mode.

27.4. CIRCULATING PUMPS

The wiring schematic provides outputs to control

the circulating pumps. The system side pump starts

immediately and after 30 seconds of operation, when

the water flow is stabilised, the pressure differential/

flow switch control function is enabled. If no alarms

are present the unit will start.

27.5. ANTI-FREEZE ALARM

The alarm

11

is always active even in standby mode.

To prevent damage to the plate heat exchanger by

freezing of the water within the unit is stopped and

an alarm raised if the water temperature drops below

the minimum anti-freeze setpoint of 3°C. The unit can

only re-start after a manual reset and if the anti-freeze

sensor reads a water temperature above 4°C

12

. With

the unit in off mode and with a water temperature

below 4°C the factory standard fitted electric heaters

on the heat exchanger are turned on, and turned off

when the water temperature exceeds 5°C. The water

pump always remains active.

27.6. WATER FLOW ALARM

The unit has a low water flow rate alarm using a fac-

tory fitted differential pressure switch or flow switch.

This safety activates after the first 30 seconds of pump

operation if the water flow rate is not sufficient. The

operation of this alarm stops the compressors and the

pump.

WARNING

11

The anti-freeze setpoint

can only be adjusted by an

authorised service centre and

only after verifying that the

hydraulic circuit has the cor-

rect % of anti-freeze solution.

12

If this alarm occurs immediate-

ly call the authorised technical

service assistance.

WARNING

FOR 230V/1/50Hz UNITS:

The unit is provided with a compres-

sor soft starter. This device contains

capacitors that could overheat

through repeated quick starts. If

power supply is removed wait at

least 3 minutes before powering up.