85

EcoChill Installation Manual 7481930_v1.6.0_08_2013

ECL-ECLH 020-202

EN

31. PROCEDURE FOR SELECTION OF SYSTEM TYPE

Several parameters of the MODU CONTROL board

have to be set, based on the type of system the unit is

installed.

These changes of parameters are summarised in the

table below to permit the installer to make the appro-

priate selections of the unit's electronic circuit board.

31.1. HOW TO MODIFY A USER MENU

PARAMETER

To access the USER setting press the key and

confirm the password 000 pressing the key . The

display will show the parameters of the USER index

as three identifying characters; the index remains dis-

played for a second and then is replaced by the value

of the parameter it relates to.

To move to the following parameter use the arrow keys

. To modify a parameter press the key , modify the

value using the arrow keys and confirm the modifica-

tion pressing the key . To exit the menu press the

key .

31.2. HOW TO MODIFY AN INSTALLER MENU

PARAMETER

To enter and modify the INSTALLER menu follow the

same procedure as the USER menu above.

Password INSTALLER menu: 030

QUESTION

ANSWER

WHAT TO DO

(1) What type of terminals are

installed in the heating circuit?

• The unit is a cooling only model

• Go to question 2

• Radiant panels

• Enter in parameter StC (index 3 menu USER) with the value of 35 °C

• Fan coil units or low temperature

radiators

• Enter in parameter StC (index 3 menu USER) with the value of 45 °C (default value)

• Other applications

• Enter in parameter StC (index 3 menu USER) with the value of 55 °C

(2) Is the remote control accessory

panel installed (PR3)?

• Not installed

• Go to question 3

• Installed

• Enter in parameter PAN (index 9 menu INSTALLER) with the appropriate value:

Value (1):

• Season selection controlled from the unit circuit board

• ON/OFF control from the PR3

Value (2):

• Season selection controlled from the PR3

• ON/OFF control from the unit circuit board

Value (3):

• Season selection controlled from the PR3

• ON/OFF control from the PR3

(3) Is domestic hot water produc-

tion present?

• Not present

• Go to question 5

• Present

• Enter in parameter ASA (menu INSTALLER) with the value (1)

(4) In the domestic hot water circuit

is a three way diverting valve

present?

• Not present

• Go to question 5

• Present

• Enter in parameter AAS (index C menu INSTALLER) with the appropriate value (in seconds):

this parameter shows the reversing time for the three way diverting valve in the circuit for the

production of domestic hot water

(5) Is an ambient thermostat

present?

• Not present

• No function

• Present

• This parameter enables a digital contact ID (shown on the electrical schematic with the

reference TRA) onto which to connect an ambient thermostat with which to disable the

compressors and electric heaters. Enter in parameter trA (index D menu INSTALLER), with the

appropriate value selecting from:

1. Value (1 or 2): ENABLED

2. Value (0 or 3): DISABLED

3. It is reminded that the OPEN state of the contact represents:

stops compressors and heaters if the parameter value is set to 1

stops compressors, pump and heaters if the parameter value is set to 2

pump alarm (as in the previous software version), if the parameter value is set to 3

WARNING

For more information refer to the USER manual provided with the unit and available on the website