Soluzione di glicole etilenico, Come leggere le curve del glicole, Ethylene glycol solution – Airedale EcoChill 6kW - 46kW User Manual

Page 53: How to read the diagram

Advertising
background image

53

EcoChill Installation Manual 7481930_v1.6.0_08_2013

ECL-ECLH 020-202

EN

12. ETHYLENE GLYCOL SOLUTION

The correction factors for cooling capacity and

power input take into account the presence of

glycol and the different evaporating tempera-

tures.

The correction factor for pressure drop takes

into account the different flow rates derived

from the application of the correction factor for

flow rates.

The correction factor for water flow rate is

calculated to maintain the same ∆t that would

be without glycol.

NOTE:

To understand how to read the diagram an example is

given below.

Using the diagram the necessary percentage of glycol

can be determined, taking into consideration one of the

two following factors:

Based on the fluid considered (water or air) enter the

diagram from the right or the left and intersect the

leaving water temperature or external air temperature

curve and draw a vertical line from this point to identify

the glycol percentage and the relative correction fac-

tors.

11.3. HOW TO READ THE DIAGRAM

The curves shown on the diagram summarise a large

quantity of data, with each curve representing a par-

ticular function, for whose correct understanding it is

necessary to make certain initial considerations:

In case the percentage glycol required is based on

external air temperature enter the diagram horizontal-

ly from the left to intersect the curve and draw a verti-

cal line through this point. The intersections with the

curves above present the correction factors for cooling

capacity, power input, pressure drop and flow rate (the

correction factors are applied to the nominal perfor-

mance data of the unit size in consideration). The inter-

section with the curve below gives the recommended

percentage of glycol for the external air temperature.

In case the percentage glycol required is based on the

leaving liquid temperature enter the diagram horizon-

tally from the right to intersect the curve and draw a

vertical line through this point. The intersections with

the curves above present the correction factors for

cooling capacity, power input, pressure drop and flow

rate (the correction factors are applied to the nominal

performance data of the unit size in consideration).

The intersection with the curve below gives the rec-

ommended percentage of glycol for the leaving liquid

temperature.

It is reminded that the initial parameters of "EXTER-

NAL AIR TEMPERATURE" and "LEAVING LIQUID

TEMPERATURE" are not linked with each other

so it is not possible to enter the diagram from one

parameter to determine the corresponding value of

the other.

2.20
2.10
2.00
1.90
1.80
1.70

1.60
1.50
1.40
1.30
1.20

1.10

1.00
0.99
0.98
0.97
0.96
0.95
0.94

5
0

-5

-10

-15
-20
-25
-30
-35
-40

0

5

10

15

20

25

30

35

40

45

50

55

-6

0

5

Pc

Ph

Qw (2)

Qw (1)

∆P (5)

∆P (4)

∆P (3)

∆P (2)

∆P (1)

Pe

LE

AVING

LIQUID

TEMPERA

TURE

EXTERN

AL

AIR

TEMPERA

TURE

Glycol %

Corr

ection f

act

or

s

LEGEND:

Pc

Correction factor cooling capacity

Pe

Correction factor power input

Ph

Correction factor heating capacity

ΔP (1) Correction factor pressure drop with average fluid temperature = -3.5 °C

ΔP (2) Correction factor pressure drop with average fluid temperature = 0.5 °C

ΔP (3) Correction factor pressure drop with average fluid temperature = 5.5 °C

ΔP (4) Correction factor pressure drop with average fluid temperature = 9.5 °C

ΔP (5) Correction factor pressure drop with average fluid temperature = 47.5 °C

Qw (1) Correction factor flow rate (evaporator) with average fluid temperature = 9.5 °C

Qw (2) Correction factor flow rate (condenser) with average fluid temperature = 47.5 °C

NOTE

Although the diagram goes down to external air temperatures of -40 °C refer to the operating limits of

the unit.

Advertising