Ecl 152 h, Standard - cooling mode, With pump – Airedale EcoChill 6kW - 46kW User Manual
Page 39: With buffer tank and pump, Cooling mode, With high head pump, N - with buffer tank and high head pump
39
EcoChill Installation Manual 7481930_v1.6.0_08_2013
ECL-ECLH 020-202
EN
10.24. ECL 152 H
version
STANDARD - COOLING MODE
(400V/3/N/50Hz)
10.25. ECL 152 H
WITH PUMP
version
P
-
WITH BUFFER TANK AND PUMP
version
A
COOLING MODE
(400V/3/N/50Hz)
10.26. ECL 152 H
WITH HIGH HEAD PUMP
version
N - WITH BUFFER TANK AND HIGH HEAD PUMP
version
Q
COOLING MODE
(400V/3/N/50Hz)
TWP
EXTERNAL AIR TEMPERATURE (°C)
FROM -10°C TO 20°C
25
30
35
40
45
46
GL
YC
OL
%
Pc
(kW)
Pe
(kW)
EER
Pc
(kW)
Pe
(kW)
EER
Pc
(kW)
Pe
(kW)
EER
Pc
(kW)
Pe
(kW)
EER
Pc
(kW)
Pe
(kW)
EER
Pc
(kW)
Pe
(kW)
EER
Pc
(kW)
Pe
(kW)
EER
4
10
35,70 7,42 4,81 33,69 8,40 4,01 31,65 9,38 3,37 29,60 10,29 2,88 27,54 11,09 2,48 25,51 11,65 2,19 25,12 11,72 2,14
6
0
37,56 7,47 5,03 35,45 8,45 4,19 33,31 9,45 3,52 31,16 10,39 3,00 29,02 11,20 2,59 26,91 11,78 2,28 26,49 11,87 2,23
7
0
38,28 7,50 5,11 36,13 8,48 4,26 33,96 9,49 3,58 31,71 10,48 3,02 29,60 11,25 2,63 27,46 11,85 2,32 27,04 11,93 2,27
8
0
38,99 7,64 5,11 36,81 8,61 4,28 34,60 9,58 3,61 32,38 10,50 3,08 30,18 11,29 2,67 28,01 11,87 2,36 27,58 11,96 2,31
10
0
40,39 7,75 5,21 38,14 8,72 4,37 35,87 9,70 3,70 33,59 10,61 3,17 31,33 11,38 2,75 29,11 11,95 2,44
-
-
-
12
0
41,77 7,85 5,32 39,45 8,82 4,47 37,11 9,80 3,79 34,78 10,70 3,25 32,46 11,46 2,83
-
-
-
-
-
-
14
0
43,13 7,94 5,43 40,74 8,92 4,57 38,34 9,89 3,88 35,95 10,78 3,33 33,59 11,53 2,91
-
-
-
-
-
-
16
0
44,46 8,03 5,54 42,02 9,01 4,66 39,56 9,98 3,96 37,12 10,87 3,41 34,70 11,61 2,99
-
-
-
-
-
-
18
0
45,78 8,14 5,62 43,28 9,13 4,74 40,77 10,09 4,04 38,64 10,99 3,51 35,82 11,70 3,06
-
-
-
-
-
-
TWP
EXTERNAL AIR TEMPERATURE (°C)
FROM -10°C TO 20°C
25
30
35
40
45
46
GL
YC
OL
%
Pc
(kW)
Pe
(kW)
EER
Pc
(kW)
Pe
(kW)
EER
Pc
(kW)
Pe
(kW)
EER
Pc
(kW)
Pe
(kW)
EER
Pc
(kW)
Pe
(kW)
EER
Pc
(kW)
Pe
(kW)
EER
Pc
(kW)
Pe
(kW)
EER
4
10
36,72 7,73 4,75 34,69 8,70 3,99 32,62 9,67 3,37 30,53 10,57 2,89 28,43 11,37 2,50 26,36 11,94 2,21 25,96 12,02 2,16
6
0
38,58 7,78 4,96 36,45 8,75 4,16 34,28 9,74 3,52 32,09 10,68 3,00 29,91 11,49 2,60 27,76 12,08 2,30 27,33 12,17 2,25
7
0
39,31 7,81 5,04 37,14 8,78 4,23 34,94 9,78 3,57 32,65 10,77 3,03 30,51 11,54 2,64 28,32 12,14 2,33 27,89 12,23 2,28
8
0
40,03 7,95 5,03 37,83 8,91 4,25 35,59 9,87 3,60 33,34 10,79 3,09 31,09 11,57 2,69 28,89 12,16 2,38 28,45 12,25 2,32
10
0
41,44 8,08 5,13 39,17 9,03 4,34 36,87 9,99 3,69 34,56 10,90 3,17 32,26 11,67 2,76 30,00 12,24 2,45
-
-
-
12
0
42,83 8,19 5,23 40,50 9,14 4,43 38,13 10,10 3,78 35,77 10,99 3,25 33,42 11,75 2,84
-
-
-
-
-
-
14
0
44,19 8,30 5,33 41,80 9,25 4,52 39,38 10,20 3,86 36,96 11,08 3,34 34,56 11,82 2,92
-
-
-
-
-
-
16
0
45,53 8,41 5,41 43,08 9,35 4,61 40,61 10,30 3,94 38,14 11,17 3,41 35,70 11,90 3,00
-
-
-
-
-
-
18
0
46,84 8,54 5,48 44,34 9,48 4,68 41,82 10,42 4,01 39,68 11,30 3,51 36,82 11,99 3,07
-
-
-
-
-
-
TWP
EXTERNAL AIR TEMPERATURE (°C)
FROM -10°C TO 20°C
25
30
35
40
45
46
GL
YC
OL
%
Pc
(kW)
Pe
(kW)
EER
Pc
(kW)
Pe
(kW)
EER
Pc
(kW)
Pe
(kW)
EER
Pc
(kW)
Pe
(kW)
EER
Pc
(kW)
Pe
(kW)
EER
Pc
(kW)
Pe
(kW)
EER
Pc
(kW)
Pe
(kW)
EER
4
10
36,43 7,77 4,69 34,45 8,70 3,96 32,42 9,64 3,36 30,36 10,51 2,89 28,28 11,30 2,50 26,23 11,86 2,21 25,84 11,93 2,17
6
0
38,29 7,82 4,89 36,20 8,76 4,13 34,07 9,72 3,51 31,92 10,63 3,00 29,76 11,42 2,61 27,63 12,00 2,30 27,20 12,08 2,25
7
0
39,01 7,86 4,96 36,89 8,79 4,20 34,73 9,76 3,56 32,47 10,72 3,03 30,35 11,47 2,65 28,19 12,06 2,34 27,76 12,15 2,29
8
0
39,71 8,02 4,95 37,56 8,93 4,21 35,36 9,86 3,59 33,15 10,75 3,08 30,93 11,51 2,69 28,75 12,08 2,38 28,31 12,17 2,33
10
0
41,08 8,19 5,02 38,88 9,08 4,28 36,63 10,00 3,66 34,35 10,87 3,16 32,09 11,62 2,76 29,85 12,17 2,45
-
-
-
12
0
42,41 8,36 5,08 40,17 9,22 4,36 37,87 10,12 3,74 35,54 10,98 3,24 33,23 11,71 2,84
-
-
-
-
-
-
14
0
(1)
41,43 9,36 4,43 39,09 10,24 3,82 36,72 11,08 3,31 34,36 11,79 2,91
-
-
-
-
-
-
16
0
42,66 9,52 4,48 40,28 10,37 3,88 37,88 11,19 3,38 35,48 11,88 2,99
-
-
-
-
-
-
18
0
(1)
41,46 10,53 3,94 39,39 11,34 3,47 36,59 11,99 3,05
-
-
-
-
-
-
WARNING
Outputs calculated with % glycol shown in table. For temperatures and %
glycol different than shown refer to Magellano
SELECTION NOT POSSIBLE:
- Outside of operating limits
(1) Excessive water flow rate beyond operating limit of pump
(2) Insufficient water flow rate bellow operating limit of pump
LEGEND
FUNCTION
Pc
Cooling capacity in kW
Pe
Power input in kW
Operation with glycol and DCPX acessory
Operation with glycol only
Operation with DCPX accessory
TWP
Temperature of Water Produced °C
Data to UNI EN14511: 2011
ΔT WATER DIFFERENT TO NOMINAL (ΔT 5°C)
3
5
8
10
Cooling capacity correction factors
0,99
1
1,02
1,03
Input power correction factors
0,99
1
1,01
1,02
FOULING FACTORS
[K*m2]/[W] 0,00005
0,0001
0,0002
Cooling capacity correction factors
1
0,98
0,94
Input power correction factors
1
0,98
0,95