Taratura vaso d’espansione, Contenuto minimo acqua, Expansion tank pressure setting – Airedale EcoChill 6kW - 46kW User Manual

Page 54: Minimum water content

Advertising
background image

54

EcoChill Installation Manual 7481930_v1.6.0_08_2013

ECL-ECLH 020-202

EN

The standard pressure setting that the expansion tank is

pre-charged to is 1.5 bar, the maximum value is 6 bar.

The expansion tank pressure setting has to be adjusted

based on the difference in height (H) of the installation

(see figure) according to the formula:

p (rating) [bar] = H [m] / 10.2 + 0.3.

For example, if the difference in height H is 20 m then the

value of the expansion tank pressure setting p is 2.3 bar.

If the calculated pressure setting value is less than 1.5 bar

(when H < 12.25), maintain the standard pressure setting

13. EXPANSION TANK PRESSURE SETTING

LEGEND
(1)

Ensure highest system point
does not exceed 55 m difference.

(2) Ensure that the lowest point of the

system can handle the total pres-
sure.

14. MINIMUM WATER CONTENT

ECL|ECLH

020

025

030

040

050

070

080

090

102

152

202

Number of compressors

1

1

1

1

1

1

1

1

2

2

2

Minimum recommended water content

l/kW

4

4

4

4

4

4

4

4

4

4

4

WARNING

t is recommended to design for

a high system water content (the

table shows the minimum recom-

mended), to limit:

1. The frequency of changes in

operating modes.

2. The reduction of water tem-

perature during the defrost

cycle in winter periods.

Hmax1 = 55m

H = 12,25m

Hmin2

H

ECL 020-025-030
Hydraulic height

H m

30

25

20

15

≥ 12.25

Expansion tank setting

bar

3.2

2.8

2.3

1.8

1.5

Water content reference value

l

(1)

103

121

139

158

168

Water content reference value

l

(2)

46

55

63

71

76

ECL 040-050-080-090
Hydraulic height

H m

30

25

20

15

≥ 12.25

Expansion tank setting

bar

3.2

2.8

2.3

1.8

1.5

Water content reference value

l

(1)

257

303

348

394

419

Water content reference value

l

(2)

116

136

157

177

189

Glycol mix

Water temperature °C

Correction factor Reference condition

max.

min.

10%

40

-2

0,507

(1)

10%

60

-2

0,686

(2)

20%

40

-6

0,434

(1)

20%

60

-6

0,604

(2)

35%

40

-6

0,393

(1)

35%

60

-6

0,555

(2)

Reference operating conditions:

(1) Cooling: Maximum water temperature = 40 °C, minimum water temperature = 4 °C.

(2) Heating (heat pump): Maximum water temperature = 60 °C, minimum water temperature = 4 °C

Advertising