TAE (°C)
LEAVING WATER TEMPERATURE (°C)
25
30
35
40
45
50
GL
YC
OL
%
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
-10
0
18,70
4,54
4,12
18,40
6,66
2,76
-
-
-
-
-
-
-
-
-
-
-
-
-8
0
19,88
4,55
4,37
19,45
6,67
2,92
19,01
7,69
2,47
-
-
-
-
-
-
-
-
-
-6
0
21,04
4,57
4,60
20,48
6,68
3,06
19,96
7,70
2,59
19,43
8,17
2,38
18,85
8,64
2,18
-
-
-
-4
0
22,18
4,59
4,83
21,50
6,70
3,21
20,90
7,72
2,71
20,32
8,19
2,48
19,73
8,66
2,28
19,10
9,68
1,97
-2
0
23,31
4,61
5,05
22,51
6,72
3,35
21,82
7,74
2,82
21,20
8,21
2,58
20,60
8,68
2,37
20,00
9,69
2,06
0
0
24,43
4,64
5,26
23,51
6,75
3,48
22,74
7,76
2,93
22,07
8,23
2,68
21,47
8,70
2,47
20,90
9,71
2,15
2
0
24,28
4,65
5,23
24,12
6,77
3,57
23,70
7,78
3,04
23,12
8,25
2,80
22,50
8,72
2,58
21,93
9,74
2,25
4
0
29,34
4,76
6,17
28,73
6,87
4,18
28,20
7,88
3,58
27,69
8,35
3,32
27,15
8,81
3,08
26,54
9,83
2,70
6
0
31,18
4,81
6,48
30,47
6,91
4,41
29,84
7,93
3,77
29,24
8,39
3,49
28,62
8,85
3,23
27,92
9,86
2,83
7
0
32,05
4,83
6,63
31,29
6,94
4,51
30,60
8,04
3,71
29,96
8,41
3,56
29,31
8,87
3,30
28,55
9,88
2,89
8
0
32,89
4,86
6,77
32,07
6,96
4,61
31,34
7,97
3,93
30,64
8,43
3,63
29,92
8,89
3,37
29,15
9,90
2,94
10
0
34,51
4,91
7,03
33,57
7,01
4,79
32,73
8,01
4,08
31,92
8,47
3,77
31,11
8,93
3,49
30,24
9,93
3,04
12
0
36,08
4,96
7,27
35,01
7,05
4,96
34,05
8,05
4,23
33,14
8,51
3,90
32,23
8,96
3,60
31,26
9,97
3,14
14
0
37,64
5,01
7,51
36,45
7,10
5,13
35,36
8,09
4,37
34,34
8,54
4,02
33,31
9,00
3,70
32,25
10,00
3,23
16
0
39,23
5,06
7,75
37,91
7,15
5,31
36,70
8,14
4,51
35,55
8,58
4,14
34,41
9,03
3,81
33,24
10,02
3,32
18
0
40,91
5,12
7,99
39,44
7,19
5,48
38,10
8,18
4,66
36,82
8,62
4,27
35,57
9,06
3,92
34,27
10,05
3,41
20
0
42,72
5,18
8,25
41,10
7,24
5,67
39,61
8,22
4,82
38,20
8,66
4,41
36,82
9,10
4,05
35,41
10,08
3,51
21 TO 42
0
42,72
5,18
8,25
41,10
7,24
5,67
39,61
8,22
4,82
38,20
8,66
4,41
36,82
9,10
4,05
35,41
10,08
3,51
TAE (
°C)
LEAVING WATER TEMPERATURE (°C)
25
30
35
40
45
50
GL
YC
OL
%
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
-10
0
(2)
(2)
-
-
-
-
-
-
-
-
-
-
-
-
-8
0
(2)
-
-
-
-
-
-
-
-
-
-6
0
(2)
(2)
-
-
-
-4
0
(2)
-2
0
0
0
23,86
4,65
5,13
22,95
6,76
3,39
2
0
23,71
4,66
5,09
23,56
6,78
3,47
23,14
7,80
2,97
4
0
28,72
4,77
6,02
28,11
6,87
4,09
27,59
7,89
3,50
27,08
8,35
3,24
26,55
8,82
3,01
25,94
9,83
2,64
6
0
30,56
4,83
6,33
29,85
6,93
4,31
29,22
7,93
3,68
28,62
8,40
3,41
28,00
8,86
3,16
27,31
9,87
2,77
7
0
31,42
4,86
6,47
30,66
6,95
4,41
29,98
8,06
3,72
29,33
8,42
3,48
28,69
8,88
3,23
27,93
9,89
2,83
8
0
32,27
4,89
6,59
31,44
6,98
4,50
30,71
7,98
3,85
30,01
8,44
3,56
29,30
8,90
3,29
28,52
9,90
2,88
10
0
33,90
4,97
6,82
32,95
7,05
4,67
32,10
8,04
3,99
31,29
8,49
3,69
30,48
8,94
3,41
29,61
9,94
2,98
12
0
35,49
5,06
7,01
34,40
7,12
4,83
33,43
8,10
4,13
32,51
8,54
3,81
31,59
8,98
3,52
30,63
9,98
3,07
14
0
(1)
35,87
7,21
4,98
34,75
8,16
4,26
33,71
8,59
3,92
32,68
9,03
3,62
31,61
10,01
3,16
16
0
(1)
36,12
8,25
4,38
34,94
8,65
4,04
33,78
9,07
3,72
32,60
10,05
3,24
18
0
(1)
36,24
8,73
4,15
34,95
9,13
3,83
33,64
10,09
3,33
20
0
(1)
36,23
9,20
3,94
34,79
10,14
3,43
21 TO 42
0
(1)
(1)
(1)
(1)
36,23
9,20
3,94
34,79
10,14
3,43
TAE (
°C)
LEAVING WATER TEMPERATURE (°C)
25
30
35
40
45
50
GL
YC
OL
%
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
-10
0
(2)
(2)
-
-
-
-
-
-
-
-
-
-
-
-
-8
0
(2)
-
-
-
-
-
-
-
-
-
-6
0
(2)
(2)
-
-
-
-4
0
(2)
-2
0
0
0
23,71
5,02
4,73
22,80
7,12
3,20
2
0
23,57
5,02
4,69
23,41
7,14
3,28
22,99
8,16
2,82
4
0
28,59
5,19
5,51
27,98
7,29
3,84
27,45
8,29
3,31
26,94
8,75
3,08
26,41
9,21
2,87
25,79
10,22
2,53
6
0
30,44
5,28
5,77
29,72
7,36
4,04
29,09
8,36
3,48
28,49
8,81
3,23
27,86
9,27
3,01
27,17
10,27
2,65
7
0
31,32
5,33
5,88
30,54
7,41
4,12
29,85
8,48
3,52
29,20
8,85
3,30
28,56
9,30
3,07
27,80
10,29
2,70
8
0
32,17
5,38
5,98
31,33
7,45
4,21
30,59
8,44
3,63
29,89
8,88
3,37
29,17
9,32
3,13
28,39
10,32
2,75
10
0
33,82
5,49
6,17
32,85
7,54
4,36
31,99
8,51
3,76
31,18
8,95
3,49
30,36
9,38
3,24
29,49
10,37
2,84
12
0
35,44
5,62
6,31
34,33
7,64
4,49
33,34
8,60
3,88
32,41
9,02
3,59
31,48
9,44
3,33
30,51
10,42
2,93
14
0
(1)
35,82
7,77
4,61
34,68
8,69
3,99
33,62
9,09
3,70
32,58
9,51
3,43
31,50
10,47
3,01
16
0
(1)
36,07
8,81
4,09
34,87
9,18
3,80
33,69
9,58
3,52
32,50
10,53
3,09
18
0
(1)
36,19
9,29
3,89
34,88
9,66
3,61
33,55
10,59
3,17
20
0
(1)
36,18
9,76
3,71
34,71
10,66
3,25
21 TO 42
0
(1)
(1)
(1)
(1)
36,18
9,76
3,71
34,71
10,66
3,25
10.50. ECL 102 H
WITH PUMP
version
P
-
WITH BUFFER TANK AND PUMP
version
A HEATING MODE
(400V/3/N/50Hz)
10.51. ECL 102 H
WITH PUMP
version
N
-
WITH BUFFER TANK AND HIGH HEAD PUMP
version
Q HEATING MODE
(400V/3/N/50Hz)
10.52. ECL 102 H
version
STANDARD - HEATING MODE
(400V/3/N/50Hz)
LEGEND
FUNCTION
Operation with DCPX accessory
TAE
Temperature of Air External in °C
Data to UNI EN14511: 2011
WARNING
Outputs calculated with % glycol shown in table. For temperatures and % glycol differ-
ent than shown refer to Magellano
SELECTION NOT POSSIBLE:
- Outside of operating limits
(1) Excessive water flow rate beyond operating limit of pump
(2) Insufficient water flow rate bellow operating limit of pump
ΔT WATER DIFFERENT TO NOMINAL (ΔT 5°C)
3
5
8
10
Heating capacity correction factors
0,99
1
1,01
1,02
Input power correction factors
1,01
1
0,98
0,96