23. ELECTRICAL CONNECTIONS

The ECL units are fully factory wired and only require

connection to the power supply network, downstream

of an isolator, in accordance with the applicable wiring

standards of the country of installation.

It is recommended to check the following items:

1.

The electrical network is capable of meeting the

electrical input data shown in the table below.

2.

The unit is only powered up on completion of

any hydraulic and electrical works.

3.

Comply with the indicated phasing and earth

requirements.

4.

The power supply cable must have the appropri-

ate protection against short circuits, residual

current and earth leakage with suitable isolation

from other devices.

5.

The tolerance on the power supply voltage is

±10% of the nominal voltage rating of the unit

(for three phase units a maximum imbalance of

3% between phases is permitted). If these values

are not met please contact the power supply

company.

6.

For the electrical connections use double insu-

lated cables in accordance with applicable wiring

standards.

MANDATORY REQUIREMENTS

1.

A magneto-thermal circuit breaker conforming

to IEC-EN standards (contact aperture minimum

3 mm) is required, with adequate protection in

accordance with the data provided in the follow-

ing table, to be installed as close as possible to

the unit.

2.

An effective earth connection is required. The

manufacturer cannot be held responsible for

any damages caused by lack of, or inadequate,

earthing of the unit.

3.

For three phase units check the correct cable

phasing.

The cable cross sections shown in the following cable

are the recommended values based on a maximum 50

m cable length.

For longer cable lengths or different types of cable

installations, the DESIGNER is responsible for correctly

sizing the isolator, circuit breaker, earthing protection

and cable sizes, based on:

Length

Type of cable

Electrical input of the unit, distance and operat-

ing ambients.

All electrical works must be carried out by PERSONNEL WITH THE APPROPRIATE LEGAL

QUALIFICATIONS, trained and aware of the risks relating to such works.

The design of the cabling and related components must be carried out by PERSONNEL WITH

APPROPRIATE QUALIFICATIONS TO DESIGN ELECTRICAL INSTALLATIONS, following interna-

tional and national standards of the location the unit is installed, in accordance with current

legal requirements.

For installation details refer to the electrical wiring schematics supplied with the unit. The

electrical wiring schematic together with the manuals must be conserved with care and

MADE AVAILABLE FOR FUTURE REFERENCE.

The weatherproof seals of the equipment must be checked before making electrical connec-

tions and the unit most only be powered on completion of all electrical and hydraulic works.

WARNING

Verify that all terminals are tight

on power carrying conductors be-

fore first start-up and 30 days after

putting into service. Afterwards

check twice yearly.

Loose terminals can result in

overheating of cables and com-

ponents..

WARNING

Using the water piping to earth

the unit is not permitted.