50
EcoChill Installation Manual 7481930_v1.6.0_08_2013
ECL-ECLH 020-202
EN
TAE (°C)
LEAVING WATER TEMPERATURE (°C)
25
30
35
40
45
50
GL
YC
OL
%
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
-10
0
22,56
5,35
4,22
22,19
7,85
2,83
-
-
-
-
-
-
-
-
-
-
-
-
-8
0
23,98
5,36
4,47
23,46
7,86
2,99
22,93
9,06
2,53
-
-
-
-
-
-
-
-
-
-6
0
25,38
5,38
4,72
24,71
7,87
3,14
24,08
9,08
2,65
23,44
9,63
2,43
22,74
10,19
2,23
-
-
-
-4
0
26,75
5,40
4,95
25,94
7,89
3,29
25,21
9,09
2,77
24,51
9,65
2,54
23,80
10,20
2,33
23,04
11,40
2,02
-2
0
28,11
5,43
5,18
27,15
7,92
3,43
26,32
9,12
2,89
25,57
9,67
2,64
24,85
10,22
2,43
24,13
11,42
2,11
0
0
29,46
5,46
5,40
28,36
7,95
3,57
27,42
9,14
3,00
26,62
9,69
2,75
25,90
10,25
2,53
25,21
11,45
2,20
2
0
29,29
5,47
5,36
29,10
7,97
3,65
28,59
9,17
3,12
27,89
9,72
2,87
27,14
10,27
2,64
26,45
11,47
2,31
4
0
35,38
5,59
6,33
34,65
8,08
4,29
34,01
9,28
3,67
33,40
9,83
3,40
32,75
10,38
3,15
32,01
11,58
2,76
6
0
37,60
5,65
6,65
36,75
8,14
4,52
35,99
9,33
3,86
35,26
9,88
3,57
34,52
10,43
3,31
33,68
11,62
2,90
7
0
38,65
5,68
6,80
37,73
8,16
4,62
36,91
9,53
3,87
36,13
9,90
3,65
35,35
10,45
3,38
34,44
11,64
2,96
8
0
39,67
5,71
6,95
38,68
8,19
4,72
37,79
9,38
4,03
36,95
9,92
3,72
36,09
10,47
3,45
35,15
11,66
3,01
10
0
41,61
5,77
7,22
40,48
8,24
4,91
39,46
9,43
4,19
38,50
9,97
3,86
37,52
10,51
3,57
36,48
11,70
3,12
12
0
43,50
5,82
7,47
42,22
8,29
5,09
41,06
9,47
4,33
39,97
10,01
3,99
38,87
10,55
3,68
37,70
11,73
3,21
14
0
45,38
5,88
7,71
43,95
8,35
5,27
42,64
9,52
4,48
41,40
10,05
4,12
40,17
10,59
3,79
38,89
11,77
3,30
16
0
47,30
5,94
7,96
45,71
8,40
5,44
44,25
9,57
4,62
42,87
10,10
4,25
41,50
10,63
3,91
40,08
11,80
3,40
18
0
49,33
6,00
8,22
47,56
8,45
5,63
45,94
9,62
4,78
44,40
10,14
4,38
42,89
10,66
4,02
41,33
11,83
3,49
20
0
51,50
6,07
8,49
49,55
8,51
5,82
47,76
9,67
4,94
46,07
10,18
4,52
44,40
10,70
4,15
42,70
11,87
3,60
21 TO 42
0
51,50
6,07
8,49
49,55
8,51
5,82
47,76
9,67
4,94
46,07
10,18
4,52
44,40
10,70
4,15
42,70
11,87
3,60
TAE (
°C)
LEAVING WATER TEMPERATURE (°C)
25
30
35
40
45
50
GL
YC
OL
%
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
-10
0
(2)
(2)
-
-
-
-
-
-
-
-
-
-
-
-
-8
0
23,29
5,56
4,19
22,78
8,06
2,83
(2)
-
-
-
-
-
-
-
-
-
-6
0
24,67
5,58
4,42
24,01
8,07
2,98
23,39
9,27
2,52
22,76
9,83
2,32
22,07
10,39
2,12
-
-
-
-4
0
26,02
5,60
4,65
25,22
8,09
3,12
24,50
9,29
2,64
23,81
9,85
2,42
23,12
10,40
2,22
22,36
11,60
1,93
-2
0
27,37
5,63
4,86
26,42
8,11
3,26
25,60
9,31
2,75
24,86
9,86
2,52
24,15
10,42
2,32
23,44
11,62
2,02
0
0
28,70
5,66
5,07
27,61
8,14
3,39
26,69
9,34
2,86
25,89
9,89
2,62
25,18
10,44
2,41
24,50
11,64
2,10
2
0
28,53
5,67
5,03
28,34
8,17
3,47
27,83
9,37
2,97
27,15
9,92
2,74
26,40
10,47
2,52
25,72
11,67
2,20
4
0
34,59
5,84
5,92
33,85
8,32
4,07
33,21
9,51
3,49
32,60
10,05
3,24
31,96
10,60
3,02
31,22
11,79
2,65
6
0
36,82
5,94
6,20
35,95
8,40
4,28
35,19
9,58
3,67
34,46
10,12
3,41
33,71
10,66
3,16
32,88
11,84
2,78
7
0
37,87
5,99
6,32
36,94
8,45
4,37
36,11
9,79
3,75
35,33
10,15
3,48
34,55
10,69
3,23
33,63
11,87
2,83
8
0
38,90
6,04
6,44
37,89
8,49
4,46
37,00
9,66
3,83
36,15
10,19
3,55
35,29
10,72
3,29
34,35
11,90
2,89
10
0
40,88
6,16
6,64
39,72
8,59
4,62
38,68
9,75
3,97
37,71
10,26
3,67
36,72
10,78
3,41
35,67
11,95
2,98
12
0
42,84
6,31
6,79
41,50
8,70
4,77
40,31
9,84
4,10
39,19
10,34
3,79
38,07
10,85
3,51
36,90
12,00
3,07
14
0
(1)
43,29
8,85
4,89
41,92
9,94
4,22
40,65
10,42
3,90
39,39
10,91
3,61
38,09
12,06
3,16
16
0
(1)
43,60
10,08
4,33
42,14
10,52
4,01
40,73
10,99
3,71
39,29
12,12
3,24
18
0
(1)
43,75
10,65
4,11
42,16
11,08
3,81
40,56
12,19
3,33
20
0
(1)
43,73
11,19
3,91
41,96
12,27
3,42
21 TO 42
0
(1)
(1)
(1)
(1)
43,73
11,19
3,91
41,96
12,27
3,42
TAE (
°C)
LEAVING WATER TEMPERATURE (°C)
25
30
35
40
45
50
GL
YC
OL
%
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
Ph
(kW)
Pe
(kW)
COP
-10
0
(2)
(2)
-
-
-
-
-
-
-
-
-
-
-
-
-8
0
23,19
5,66
4,10
22,69
8,16
2,78
(2)
-
-
-
-
-
-
-
-
-
-6
0
24,56
5,67
4,33
23,91
8,17
2,93
23,29
9,38
2,48
22,66
9,94
2,28
(2)
-
-
-
-4
0
25,90
5,69
4,55
25,11
8,18
3,07
24,39
9,39
2,60
23,71
9,95
2,38
23,02
10,51
2,19
(2)
-2
0
27,24
5,71
4,77
26,30
8,20
3,21
25,48
9,40
2,71
24,75
9,96
2,48
24,05
10,52
2,29
23,34
11,72
1,99
0
0
28,56
5,74
4,98
27,47
8,23
3,34
26,56
9,42
2,82
25,77
9,98
2,58
25,07
10,54
2,38
24,40
11,74
2,08
2
0
28,38
5,74
4,94
28,20
8,24
3,42
27,70
9,45
2,93
27,02
10,00
2,70
26,28
10,56
2,49
25,61
11,76
2,18
4
0
34,37
5,86
5,86
33,65
8,35
4,03
33,02
9,55
3,46
32,42
10,10
3,21
31,78
10,65
2,98
31,05
11,85
2,62
6
0
36,56
5,93
6,17
35,72
8,41
4,25
34,97
9,60
3,64
34,25
10,15
3,38
33,52
10,69
3,13
32,69
11,89
2,75
7
0
37,60
5,96
6,31
36,69
8,44
4,35
35,87
9,80
3,67
35,10
10,17
3,45
34,34
10,72
3,20
33,44
11,91
2,81
8
0
38,60
5,99
6,44
37,62
8,47
4,44
36,74
9,65
3,81
35,91
10,19
3,52
35,07
10,74
3,27
34,14
11,93
2,86
10
0
40,53
6,06
6,68
39,41
8,53
4,62
38,40
9,71
3,96
37,44
10,24
3,66
36,48
10,78
3,38
35,45
11,97
2,96
12
0
42,40
6,14
6,91
41,13
8,59
4,79
39,98
9,76
4,09
38,89
10,29
3,78
37,80
10,83
3,49
36,66
12,00
3,05
14
0
44,28
6,22
7,12
42,84
8,66
4,95
41,55
9,82
4,23
40,32
10,34
3,90
39,10
10,87
3,60
37,82
12,04
3,14
16
0
46,20
6,31
7,32
44,60
8,74
5,11
43,14
9,89
4,36
41,77
10,40
4,02
40,41
10,91
3,70
39,00
12,08
3,23
18
0
48,24
6,41
7,52
46,45
8,82
5,27
44,83
9,95
4,50
43,29
10,45
4,14
41,78
10,96
3,81
40,24
12,12
3,32
20
0
50,44
6,54
7,71
48,46
8,92
5,43
46,65
10,03
4,65
44,95
10,52
4,27
43,29
11,02
3,93
41,60
12,16
3,42
21 TO 42
0
50,44
6,54
7,71
48,46
8,92
5,43
46,65
10,03
4,65
44,95
10,52
4,27
43,29
11,02
3,93
41,60
12,16
3,42
10.53. ECL 152 H
WITH PUMP
version
P
-
WITH BUFFER TANK AND PUMP
version
A HEATING MODE
(400V/3/N/50Hz)
10.54. ECL 152 H
WITH PUMP
version
N
-
WITH BUFFER TANK AND HIGH HEAD PUMP
version
Q HEATING MODE
(400V/3/N/50Hz)
10.55. ECL 152 H
version
STANDARD - HEATING MODE
(400V/3/N/50Hz)
LEGEND
FUNCTION
Operation with DCPX accessory
TAE
Temperature of Air External in °C
Data to UNI EN14511: 2011
WARNING
Outputs calculated with % glycol shown in table. For temperatures and % glycol differ-
ent than shown refer to Magellano
SELECTION NOT POSSIBLE:
- Outside of operating limits
(1) Excessive water flow rate beyond operating limit of pump
(2) Insufficient water flow rate bellow operating limit of pump
ΔT WATER DIFFERENT TO NOMINAL (ΔT 5°C)
3
5
8
10
Heating capacity correction factors
0,99
1
1,01
1,02
Input power correction factors
1,01
1
0,98
0,96