22.2. INTERNAL AND EXTERNAL HYDRAULIC CIRCUIT ECL “°P|°N” / "HP|HN"

COMPONENTS PROVIDED AS STANDARD

1 Water filter

2 Differential pressure switch

3 Plate heat exchanger

4 Water temperature sensor (IN/OUT)

6 Safety valve

7 Expansion tank

8 Air vent

12 Pump

COMPONENTS NOT PROVIDED AND RESPONSIBILITY OF THE INSTALLER

5 Anti-vibration joints

7 Additional expansion tank (if necessary)

9 System buffer tank

10 Drain valve

11 Isolating valve

13 Gauge

HYDRAULIC

COMPONENTS ECL

HYDRAULIC COMPONENTS

RECOMMENDED EXTERNAL TO UNIT

WARNING

The selection and installation

of components external to the

ECL°P|N /ECLHP|HN unit are the

responsibility of the installer and

must be carried out in accord-

ance with good working practices

and applicable standards of the

country of destination.

WARNING

The hydraulic piping to the unit

must be adequately sized for the

required flow rate. The water flow

rate through the heat exchanger

must always be constant.

WARNING

Carefully clean the system prior to

connection to the unit. This clean-

ing eliminates welding slag, dirt,

rust or any other impurities from

the piping. These impurities may

otherwise be deposited within

the unit and cause a malfunction

The connecting piping must be

adequately supported so as not to

impose any weight onto the unit.

3

PD

4

4

12

5

5

1

8

13

7

11

6

8

9

10

11

13

8

7