Ecl 102 h, Standard - cooling mode, With pump – Airedale EcoChill 6kW - 46kW User Manual

Page 38: With buffer tank and pump, Cooling mode, With high head pump, N - with buffer tank and high head pump

Advertising
background image

38

EcoChill Installation Manual 7481930_v1.6.0_08_2013

ECL-ECLH 020-202

EN

10.21. ECL 102 H

version

STANDARD - COOLING MODE

(400V/3/N/50Hz)

10.22. ECL 102 H

WITH PUMP

version

P

-

WITH BUFFER TANK AND PUMP

version

A

COOLING MODE

(400V/3/N/50Hz)

10.23. ECL 102 H

WITH HIGH HEAD PUMP

version

N - WITH BUFFER TANK AND HIGH HEAD PUMP

version

Q

COOLING MODE

(400V/3/N/50Hz)

TWP

EXTERNAL AIR TEMPERATURE (°C)

FROM -10°C TO 20°C

25

30

35

40

45

46

GL

YC

OL

%

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

4

10

28,99 6,24 4,65 27,36 7,07 3,87 25,71 7,89 3,26 24,04 8,65 2,78 22,37 9,32 2,40 20,72 9,80 2,11 20,41 9,85 2,07

6

0

30,50 6,28 4,86 28,79 7,11 4,05 27,06 7,95 3,40 25,31 8,74 2,90 23,57 9,41 2,50 21,85 9,91 2,21 21,51 9,98 2,16

7

0

31,09 6,31 4,93 29,35 7,13 4,11 27,58 7,98 3,46 25,75 8,82 2,92 24,04 9,46 2,54 22,30 9,96 2,24 21,96 10,03 2,19

8

0

31,66 6,42 4,93 29,89 7,24 4,13 28,10 8,06 3,49 26,30 8,83 2,98 24,51 9,49 2,58 22,75 9,98 2,28 22,40 10,05 2,23

10

0

32,80 6,52 5,03 30,98 7,34 4,22 29,13 8,16 3,57 27,28 8,92 3,06 25,44 9,57 2,66 23,64 10,05 2,35

-

-

-

12

0

33,92 6,60 5,14 32,04 7,42 4,32 30,14 8,24 3,66 28,24 9,00 3,14 26,36 9,64 2,74

-

-

-

-

-

-

14

0

35,02 6,68 5,24 33,09 7,50 4,41 31,14 8,32 3,74 29,20 9,07 3,22 27,28 9,70 2,81

-

-

-

-

-

-

16

0

36,11 6,76 5,34 34,12 7,58 4,50 32,13 8,40 3,83 30,14 9,14 3,30 28,19 9,76 2,89

-

-

-

-

-

-

18

0

37,17 6,85 5,43 35,14 7,68 4,58 33,11 8,49 3,90 31,48 9,24 3,40 29,09 9,84 2,96

-

-

-

-

-

-

TWP

EXTERNAL AIR TEMPERATURE (°C)

FROM -10°C TO 20°C

25

30

35

40

45

46

GL

YC

OL

%

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

4

10

29,59 6,29 4,70 27,96 7,10 3,94 26,29 7,91 3,32 24,61 8,67 2,84 22,92 9,34 2,45

(2)

(2)

6

0

31,09 6,33 4,91 29,38 7,14 4,11 27,64 7,98 3,46 25,88 8,77 2,95 24,12 9,44 2,55

7

0

31,68 6,36 4,98 29,95 7,17 4,18 28,17 8,01 3,52 26,33 8,84 2,98 24,60 9,48 2,59

8

0

32,26 6,48 4,98 30,49 7,28 4,19 28,69 8,09 3,55 26,88 8,85 3,04 25,08 9,51 2,64

10

0

33,39 6,60 5,06 31,58 7,39 4,28 29,73 8,19 3,63 27,87 8,95 3,12 26,02 9,59 2,71 24,19 10,07 2,40

-

-

-

12

0

34,50 6,70 5,15 32,64 7,48 4,36 30,74 8,28 3,71 28,84 9,02 3,20 26,95 9,66 2,79

-

-

-

-

-

-

14

0

35,57 6,81 5,22 33,68 7,58 4,44 31,74 8,36 3,80 29,80 9,10 3,27 27,87 9,72 2,87

-

-

-

-

-

-

16

0

(1)

34,70 7,68 4,52 32,73 8,45 3,87 30,75 9,18 3,35 28,78 9,79 2,94

-

-

-

-

-

-

18

0

35,69 7,81 4,57 33,70 8,56 3,93 32,09 9,29 3,46 29,69 9,87 3,01

-

-

-

-

-

-

TWP

EXTERNAL AIR TEMPERATURE (°C)

FROM -10°C TO 20°C

25

30

35

40

45

46

GL

YC

OL

%

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

4

10

29,69 6,75 4,40 28,08 7,53 3,73 26,42 8,32 3,18 24,75 9,05 2,74 23,06 9,71 2,37

(2)

(2)

6

0

31,20 6,80 4,59 29,50 7,58 3,89 27,77 8,38 3,31 26,02 9,15 2,84 24,26 9,81 2,47

7

0

31,78 6,83 4,66 30,06 7,61 3,95 28,30 8,42 3,36 26,47 9,23 2,87 24,74 9,85 2,51

8

0

32,35 6,96 4,65 30,60 7,72 3,96 28,82 8,51 3,39 27,02 9,25 2,92 25,22 9,89 2,55

10

0

33,47 7,10 4,71 31,68 7,85 4,03 29,85 8,62 3,46 28,00 9,35 2,99 26,16 9,98 2,62 24,34 10,44 2,33

-

-

-

12

0

34,56 7,23 4,78 32,73 7,97 4,11 30,85 8,73 3,53 28,97 9,44 3,07 27,08 10,05 2,69

-

-

-

-

-

-

14

0

35,62 7,37 4,83 33,76 8,09 4,17 31,85 8,83 3,61 29,92 9,53 3,14 28,00 10,13 2,77

-

-

-

-

-

-

16

0

(1)

34,76 8,21 4,23 32,82 8,94 3,67 30,86 9,63 3,21 28,91 10,20 2,83

-

-

-

-

-

-

18

0

35,74 8,37 4,27 33,78 9,07 3,72 32,19 9,76 3,30 29,81 10,30 2,90

-

-

-

-

-

-

WARNING

Outputs calculated with % glycol shown in table. For temperatures and %

glycol different than shown refer to Magellano

SELECTION NOT POSSIBLE:

- Outside of operating limits

(1) Excessive water flow rate beyond operating limit of pump

(2) Insufficient water flow rate bellow operating limit of pump

LEGEND

FUNCTION

Pc

Cooling capacity in kW

Pe

Power input in kW
Operation with glycol and DCPX acessory
Operation with glycol only

Operation with DCPX accessory

TWP

Temperature of Water Produced °C

Data to UNI EN14511: 2011

ΔT WATER DIFFERENT TO NOMINAL (ΔT 5°C)

3

5

8

10

Cooling capacity correction factors

0,99

1

1,02

1,03

Input power correction factors

0,99

1

1,01

1,02

FOULING FACTORS

[K*m2]/[W] 0,00005

0,0001

0,0002

Cooling capacity correction factors

1

0,98

0,94

Input power correction factors

1

0,98

0,95