Ecl 152 cooling only, Standard, Ecl 152 cooling only with pump – Airedale EcoChill 6kW - 46kW User Manual

Page 28: With pump and buffer tank, Ecl 152 cooling only with high head pump, With high head pump and buffer tank

Advertising
background image

28

EcoChill Installation Manual 7481930_v1.6.0_08_2013

ECL-ECLH 020-202

EN

TWP

EXTERNAL AIR TEMPERATURE (°C)

FROM -10°C TO 20°C

25

30

35

40

45

46

GL

YC

OL

%

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

-6

30

28,88 7,25 3,99 27,31 8,19 3,33 25,67 9,15 2,81 23,97 10,04 2,39

-

-

-

-

-

-

-

-

-

-4

30

30,51 7,38 4,13 28,85 8,30 3,48 27,14 9,23 2,94 25,37 10,09 2,51

-

-

-

-

-

-

-

-

-

-2

25

32,30 7,47 4,33 30,55 8,37 3,65 28,73 9,29 3,09 26,86 10,15 2,65

-

-

-

-

-

-

-

-

-

0

20

34,08 7,53 4,53 32,23 8,43 3,82 30,31 9,34 3,24 28,35 10,22 2,77 26,39 10,94 2,41

-

-

-

-

-

-

2

15

35,90 7,52 4,77 33,94 8,43 4,03 31,91 9,36 3,41 29,87 10,23 2,92 27,80 10,98 2,53

-

-

-

-

-

-

4

10

37,57 7,65 4,91 35,52 8,55 4,15 33,43 9,47 3,53 31,29 10,34 3,03 29,16 11,10 2,63 27,05 11,63 2,33 26,64 11,71 2,28

6

0

39,48 7,70 5,13 37,33 8,61 4,34 35,14 9,54 3,68 32,91 10,44 3,15 30,69 11,21 2,74 28,49 11,77 2,42 28,05 11,86 2,37

7

0

40,23 7,73 5,20 38,04 8,64 4,40 35,81 9,59 3,74 33,48 10,53 3,18 31,29 11,26 2,78 29,07 11,84 2,46 28,63 11,92 2,40

8

0

40,95 7,89 5,19 38,73 8,78 4,41 36,47 9,69 3,76 34,18 10,56 3,24 31,90 11,30 2,82 29,64 11,86 2,50 29,19 11,95 2,44

10

0

42,36 8,06 5,26 40,09 8,93 4,49 37,77 9,83 3,84 35,42 10,68 3,32 33,09 11,41 2,90 30,78 11,94 2,58

-

-

-

12

0

43,73 8,23 5,31 41,42 9,06 4,57 39,05 9,95 3,92 36,65 10,78 3,40 34,26 11,50 2,98

-

-

-

-

-

-

14

0

(1)

42,72 9,21 4,64 40,30 10,07 4,00 37,86 10,89 3,48 35,43 11,58 3,06

-

-

-

-

-

-

16

0

43,99 9,37 4,69 41,54 10,20 4,07 39,06 11,00 3,55 36,58 11,67 3,13

-

-

-

-

-

-

18

0

(1)

42,76 10,35 4,13 40,61 11,15 3,64 37,73 11,78 3,20

-

-

-

-

-

-

TWP

EXTERNAL AIR TEMPERATURE (°C)

FROM -10°C TO 20°C

25

30

35

40

45

46

GL

YC

OL

%

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

-6

30

29,10 7,26 4,01 27,50 8,23 3,34 25,84 9,21 2,81 24,12 10,10 2,39

-

-

-

-

-

-

-

-

-

-4

30

30,76 7,36 4,18 29,07 8,31 3,50 27,32 9,27 2,95 25,52 10,15 2,51

-

-

-

-

-

-

-

-

-

-2

25

32,57 7,44 4,38 30,78 8,38 3,67 28,92 9,32 3,10 27,03 10,21 2,65

-

-

-

-

-

-

-

-

-

0

20

34,36 7,49 4,59 32,46 8,44 3,85 30,51 9,38 3,25 28,52 10,27 2,78 26,53 11,02 2,41

-

-

-

-

-

-

2

15

36,16 7,51 4,81 34,16 8,45 4,04 32,10 9,41 3,41 30,03 10,29 2,92 27,94 11,06 2,53

-

-

-

-

-

-

4

10

37,86 7,60 4,98 35,77 8,54 4,19 33,63 9,50 3,54 31,47 10,40 3,03 29,31 11,16 2,63 27,18 11,72 2,32

26,77 11,80 2,27

6

0

39,77 7,65 5,20 37,58 8,60 4,37 35,35 9,57 3,69 33,09 10,49 3,16 30,84 11,28 2,74 28,62 11,86 2,41

28,18 11,94 2,36

7

0

40,53 7,68 5,28 38,30 8,63 4,44 36,02 9,61 3,75 33,66 10,58 3,18 31,45 11,33 2,78 29,20 11,92 2,45

28,76 12,00 2,40

8

0

41,27 7,82 5,28 39,00 8,75 4,45 36,69 9,70 3,78 34,37 10,60 3,24 32,06 11,36 2,82 29,78 11,94 2,49 29,33 12,02 2,44

10

0

42,73 7,95 5,38 40,39 8,88 4,55 38,02 9,82 3,87 35,63 10,70 3,33 33,26 11,46 2,90 30,93 12,01 2,57

-

-

-

12

0

44,16 8,06 5,48 41,75 8,98 4,65 39,32 9,92 3,96 36,88 10,80 3,42 34,45 11,54 2,99

-

-

-

-

-

-

14

0

45,57 8,17 5,58 43,10 9,09 4,74 40,60 10,02 4,05 38,11 10,88 3,50 35,63 11,61 3,07

-

-

-

-

-

-

16

0

46,95 8,28 5,67

44,42 9,20 4,83 41,87 10,12 4,14 39,33 10,98 3,58 36,80 11,68 3,15

-

-

-

-

-

-

18

0

48,30 8,41 5,74

45,72 9,33 4,90 43,13 10,24 4,21 40,53 11,08 3,66 37,97 11,78 3,22

-

-

-

-

-

-

TWP

EXTERNAL AIR TEMPERATURE (°C)

FROM -10°C TO 20°C

25

30

35

40

45

46

GL

YC

OL

%

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

Pc

(kW)

Pe

(kW)

EER

-6

30

28,13 6,97 4,03 26,56 7,95 3,34 24,92 8,92 2,79 23,24 9,81 2,37

-

-

-

-

-

-

-

-

-

-4

30

29,77 7,07 4,21 28,11 8,02 3,50 26,38 8,99 2,93 24,61 9,87 2,49

-

-

-

-

-

-

-

-

-

-2

25

31,55 7,15 4,41 29,78 8,10 3,68 27,97 9,05 3,09 26,11 9,94 2,63

-

-

-

-

-

-

-

-

-

0

20

33,32 7,21 4,62 31,45 8,16 3,85 29,53 9,10 3,24 27,58 9,99 2,76 25,64 10,73 2,39

-

-

-

-

-

-

2

15

35,10 7,24 4,85 33,13 8,18 4,05 31,11 9,14 3,40 29,07 10,03 2,90 27,03 10,78 2,51

-

-

-

-

-

-

4

10

36,80 7,32 5,03 34,73 8,26 4,20 32,63 9,23 3,54 30,50 10,12 3,02 28,39 10,89 2,61 26,30 11,44 2,30 25,90 11,53 2,25

6

0

38,71 7,36 5,26 36,55 8,32 4,39 34,34 9,30 3,69 32,12 10,22 3,14 29,92 11,00 2,72 27,74 11,57 2,40 27,31 11,66 2,34

7

0

39,46 7,39 5,34 37,25 8,35 4,46 35,01 9,34 3,75 32,69 10,31 3,17 30,52 11,05 2,76 28,31 11,64 2,43 27,88 11,72 2,38

8

0

40,19 7,53 5,34 37,94 8,48 4,48 35,67 9,43 3,78 33,38 10,33 3,23 31,11 11,09 2,80 28,88 11,66 2,48 28,44 11,75 2,42

10

0

41,64 7,65 5,45 39,32 8,59 4,57 36,97 9,55 3,87 34,62 10,43 3,32 32,29 11,19 2,89 30,01 11,74 2,56

-

-

-

12

0

43,06 7,74 5,56 40,67 8,70 4,68 38,26 9,65 3,97 35,85 10,53 3,41 33,46 11,27 2,97

-

-

-

-

-

-

14

0

44,45 7,84 5,67 42,00 8,79 4,78 39,53 9,74 4,06 37,06 10,61 3,49 34,62 11,34 3,05

-

-

-

-

-

-

16

0

45,83 7,93 5,78 43,31 8,89 4,87 40,78 9,83 4,15 38,26 10,70 3,58 35,78 11,41 3,13

-

-

-

-

-

-

18

0

47,19 8,04 5,87 44,61 9,00 4,96 42,02 9,94 4,23 39,83 10,80 3,69 36,92 11,50 3,21

-

-

-

-

-

-

9.24. ECL 152 COOLING ONLY

version

STANDARD

(400V/3/N/50Hz)

9.25. ECL 152 COOLING ONLY WITH PUMP

version

P

-

WITH PUMP AND BUFFER TANK

version

A

(400V/3/N/50Hz)

9.26. ECL 152 COOLING ONLY WITH HIGH HEAD PUMP

version

N

-

WITH HIGH HEAD PUMP AND BUFFER TANK

version

Q

- (400V/3/N/50Hz)

WARNING

Outputs calculated with % glycol shown in table. For temperatures and %

glycol different than shown refer to Magellano

SELECTION NOT POSSIBLE:

- Outside of operating limits

(1) Excessive water flow rate beyond operating limit of pump

LEGEND

FUNCTION

Pc

Cooling capacity in kW

Pe

Power input in kW
Operation with glycol and DCPX acessory
Operation with glycol only

Operation with DCPX accessory

TWP

Temperature of Water Produced °C

Data to UNI EN14511: 2011

ΔT WATER DIFFERENT TO NOMINAL (ΔT 5°C)

3

5

8

10

Cooling capacity correction factors

0,99

1

1,02

1,03

Input power correction factors

0,99

1

1,01

1,02

FOULING FACTORS

[K*m2]/[W] 0,00005

0,0001

0,0002

Cooling capacity correction factors

1

0,98

0,94

Input power correction factors

1

0,98

0,95

Advertising