Chapter 4 ________________________________________________________________ Operation

VAISALA_______________________________________________________________________ 49

Scaling Analog Outputs

Turn the internal Calibration Enabled/Disabled DIP switch of the
transmitter to upward position (on). Press button C on the display cover
and a text similar to the following appears:

0505-290

Numbers on the second line indicate the low end scaling of Ch 1 currently
stored in the transmitter memory. The text "Set Lo" on the lower left corner
indicates that you can now change the low end scaling with buttons Up and
Dn. Acknowledge the value with button E and a text similar to the
following appears:

0505-291

Numbers on the second line indicate the high end scaling of Ch 1. The text
"Set Hi" on the lower left-hand corner indicates that you can now change
the high end scaling with buttons Up and Dn. Acknowledge with button E.

If there is another channel available, the display shifts to the scaling menu
of Ch 2. You can now scale the analog outputs for the Ch 2 in the same way
as described above.

Press button C to exit the display command mode or continue by selecting
the output quantities. This menu starts automatically after the scaling menu
only if the output selection DIP switches are on the position special (all up)
from the beginning.

NOTE

Remember to restore the DIP switch settings.