Chapter 4 ________________________________________________________________ Operation

VAISALA_______________________________________________________________________ 51

To start issuing commands, make sure that HMT360 is connected to a
serial port of your computer and that the terminal session is open. Issue
commands by typing them on your computer according to the following
instructions. In these commands, <cr> stands for pressing Enter (on your
computer keyboard).

Setting the Analog Outputs

ASEL Selecting Analog Outputs

Syntax: ASEL [xxxyyy]<cr>

Turn the internal DIP switch Calibration Enabled/Disabled to position
ON before the selecting the analog outputs and return it to position OFF
after making the selection. Output quantities and their abbreviations are
listed in the table below:

where
xxx =

Quantity of Ch 1

yyy =

Quantity of Ch 2

Character Quantity

Abbreviation

Availability

Metric Unit

Nonmetric Unit

0

relative humidity

RH

A, D

%RH

%RH

1

temperature

T

A, D, F, H

°C

°F

2

dewpoint
temperature

Td

D

°C

°F

3

absolute humidity a

D

g/m

3

gr/ft

3

4

mixing ratio

x

D

g/kg

gr/lb

5

wet bulb
temperature

Tw

D

°C

°F

6

mass
concentration of
water

ppmw

H

ppm

w

ppm

w

7

water activity

aw

H, F

0 ... 1

0 ... 1

8

relative humidity
of saturation

RS

H

%RS

%RS

9

saturation
temperature

Ts

H

°C

°F