1-16

5708009-C

Advanced Energy

®

Conditions of Use

To be in compliance with the stated directives and standards, you must meet the
following conditions of use.

This device must be used in an overvoltage category II installation only.

Before making any other connection, connect the auxiliary Protective Earth
ground conductor on the rear panel.

Use only a shielded cable on the input power connector.

Use only a shielded power cable on the output power connector.

Install and operate this device only in a pollution degree 2 or better environment,
which means an indoor location such as a computer room, office, or factory floor
where only non-conductive pollution occurs during operation. Occasionally, a
temporary conductivity caused by condensation occurs when the device is not
operating.

Non-standard connectors for input and/or output power must be inaccessible to
the user.

If your unit does not have a circuit breaker, install and operate it with a circuit
breaker on the ac input to provide over current protection. The circuit breaker
must have a trip value as specified in the line current section of Table 3-2. on
page 3-5.