Maximum pressure rating, 9 bar (100 psi), Heat removal – Apex Digital 5708009-C User Manual

Page 43: Contaminates

Advertising
background image

5708009-C

3-11

Apex 1 to 5.5 kW Generator

Maximum pressure
rating

6.9 Bar (100 psi)

Heat removal

For 1.5 kW, 3410 BTU/hour, 1000W at full rated
output power

For 3 kW, 6825 BTU/hour, 2000W at full rated output
power

For 5.5 kW, 12,500 BTU/hour, 3660W at full rated RF
output power

Contaminates

The following specifications are recommended for the
water used to cool the Apex generator:

pH between 7 and 9

Total chlorine < 20 ppm

Total nitrate < 10 ppm

Total sulfate < 100 ppm

Total dissolved solids < 250 ppm

Total hardness expressed as calcium carbonate
equivalent less than 250 ppm

Specific resistivity of 2500

Ω/cm or higher at 25°C

Total dissolved solids (TDS) as estimated by the
following:

TDS

≤ 640,000

specific resistivity (

Ω/cm)

Table 3-5. Cooling Specification (Continued)

Description

Specification

Advertising