Balboa Water Group BP 60Hz User Manual

Page 65

Advertising
background image

65

Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417, 834 b2,

Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. All material copyright of Balboa Water Group.

42211B

A / B (A/B SENSOR TEMPERATURES)

When this is set to On, the temperature display will alternate to
display temperature from Sensor A and Sensor B in the heater.

FALT LOG (FAULT LOG)

The Fault Log is a record of the last 24 faults that can be re-
viewed by a service tech.

SCROLLING TP400/TP600 MESSAGES

The following messages will scroll across the TP400/TP600 pan-
els. NOTE: LCD readouts may look slightly different than shown
on screen.

RUN PMPS PURG AIR ----

PRIMING MODE – M019

Each time the spa is powered up, it will enter Priming Mode. The
purpose of Priming Mode is to allow the user to run each pump
and manually verify that the pumps are primed (air is purged)
and water is flowing. This typically requires observing the output
of each pump separately, and is generally not possible in normal
operation. Priming Mode lasts 4 minutes, but you can exit it
earlier by pressing any Temp button. The heater is not allowed to
run during Priming Mode.
NOTE: If your spa has a Circ Pump, it will turn on with Jets 1 in
Priming Mode. The Circ Pump will run by itself when Priming
Mode is exited.

-- -- --˚F -- -- -- ˚C

Water Temperature is Unknown

After the pump has been running for 1 minute, the temperature
will be displayed.

42˚F TOO COLD

Too Cold - Freeze Protection

A potential freeze condition has been detected, or the Aux Freeze
Switch has closed, and all pumps and blower are activated. All
pumps and blower are ON for at least 4 minutes after the poten-
tial freeze condition has ended, or when the aux freeze switch
opens. In some cases, pumps may turn on and off and the heater
may operate during Freeze Protection. This is an operational
message, not an error indication.

WATR TOO HOT -- -- -- --

Water is too Hot (OHS) – M029

One of the water temp sensors has detected spa water temp
110°F (43.3°C) and spa functions are disabled. System will auto
reset when the spa water temp is below 108°F (42.2°C). Check
for extended pump operation or high ambient temp.

SFTY TRIP -- -- -- --

Safety Trip - Pump Suction Blockage* – M033

The Safety Trip error message indicates that the vacuum switch
has closed. This occurs when there has been a suction problem
or a possible entrapment situation avoided. (Note: not all spas
have this feature.)

HTR FLOW LOSS -- -- -- --

Heater Flow is Reduced (HFL) – M016

There may not be enough water flow through the heater to carry
the heat away from the heating element. Heater start up will
begin again after about 1 min. See “Flow Related Checks” below.

HTR FLOW FAIL -- -- -- --

Heater Flow is Reduced (LF)* – M017

There is not enough water flow through the heater to carry the
heat away from the heating element and the heater has been
disabled. See “Flow Related Checks” below. After the problem
has been resolved, you must press any button to reset and begin
heater start up.

HTR MAY BE DRY -- -- -- -- WAIT -- -- -- --

Heater May be Dry (dr)* – M028

Possible dry heater, or not enough water in the heater to start
it. The spa is shut down for 15 min. Press any button to reset the
heater start-up. See “Flow Related Checks” below.

HTR TOO HOT -- -- -- --

HTR is too Hot (OHH)* M030

One of the water temp sensors has detected 118°f (47.8°C) in the
heater and the spa is shut down. You must press any button to
reset when water is below 108°f (42.2°C). See “Flow Related
Checks” below.

PRES BTTN TO RSET -- -- -- --

TP400, TP600 Messages (cont.)

Advertising