CAFS Air Bottle Installer/Operation Guide
p/n: 029-0020-85-0

In s talle r In sta llatio n

Add a service loop to avoid strain on the wires or connectors during body
and frame flex. Also see Figure 4-17: “Extra Cable Storage” on page 43.

CAFSAttack Main Wire Harness

The system installer must provide an extension main power and ground
wire cable for the Class1 CAFSAttack system. (See heading “ Primary
Power and Ground” on page 42.)
Also see Figure 4-16: “Primary CAFS
Wire Harness.”

Figure 4-16: Primary CAFS Wire Harness

Before connecting the cable harness, Class1 p/n: 112757, inspect the O-
ring seals of the female connectors. If a seal washer is missing or dam-
aged, water can enter the connector causing pin and terminal corrosion,
resulting in possible system failure.

IMPORTANT !

THE POWER MUST BE FUSED FOR 12 VDC (OR OPTIONAL 24 VDC), MINI-
MUM 20 AMP. CIRCUIT TO MEET NFPA SPECIFICATIONS. USE MINIMUM 16
AWG TYPE SXL OR GXL (SAE J1128) WIRE.

DO NOT CONNECT POWER SUPPLY HARNESS TO A “LOAD SHEDDING
SYSTEM.