The Tuba must be installed in a suitable environment and properly connected to its voltage
supplies and the motor.

3.1. Before You Begin

3.1.1.

Site Requirements

You can guarantee the safe operation of the Tuba by ensuring that it is installed in an
appropriate environment.

Feature

Value

Ambient operating temperature

0 °C to 40 °C (32 °F to 104 °F)

Maximum relative humidity

90% non-condensing

Operating area atmosphere

No flammable gases or vapors permitted in area

Models for extended environmental conditions are available.

Caution:
The Tuba dissipates its heat by forced ventilation (fan). The maximum operating
ambient temperature of 0 °C to 40 °C (32 °F to 104 °F) must not be exceeded.

3.1.2.

Hardware Requirements

3.1.2.1.

AC Input Requirements

Circuit Breakers &

Contacts

Three-Phase Supply

Voltage

Single-Phase Supply

Voltage

Circuit breaker current rating 150% to 200% of drive

current

200% to 300% of drive
current

Circuit breaker voltage rating 250 VAC / 480 VAC depending upon operating AC voltage

Contactor

Up to 150% of drive current

Up to 200% of drive current

3.1.2.2.

Recommended Wire Cross-Sections (All Models)

Feature

Connection

Details

AC input

AC1, AC2, AC3

4 to 5 mm

2

, 10 to 12 AWG

Motor

M1, M2, M3

4 to 5 mm

2

, 10 to 12 AWG

Protective earth

PE, PE

4 to 5 mm

2

, 10 to 12 AWG

Auxiliary power

24V +, –

0.5 to 1 mm

2

, 18 to 20 AWG