Where to mount the rack, Dimmer room requirements, Wire routing – ETC Sensor3 CE (ESR3) Rack User Manual

Page 12: N o t e

Advertising
background image

4

Sensor3 CE Rack (ESR3) Installation Manual

.

Where to Mount the Rack

Sensor3 dimmer racks require 25cm of top clearance

for proper airflow through the cabinet. To allow the door

to open sufficiently to install and remove modules,

install the rack with 41cm of front clearance and 15cm

clearance to the left of the door hinge from walls or

other equipment.

Dimmer Room Requirements

A main circuit breaker cabinet or other readily
accessible input power disconnect device.

A clean (not dusty) temperature-controlled
environment

Restricted public access to prevent tampering

Soundproofing or performance area separation to
muffle ventilation fan noise

Please see

Appendix A: Sensor3 CE Rack

Specifications, page 34

, for environmental details.

ESR3-12 racks are normally wall-mounted. ESR3-24

racks can be wall or pedestal mounted. ESR3-36 and

ESR3-48 racks are designed to be free standing.

Install racks with the CEM3 about 100cm from the floor. In ESR3-12 and ESR3-24 racks,

the CEM3 is in the bottom slot. In ESR3-36 and ESR3-48 racks, the CEM3 slot is in the

middle.

Wire Routing

Sensor3 racks have access panels at the top and bottom, and conduit knockouts at the

side. Line and load wiring can enter from the top or bottom. Control cables can enter from

the top, bottom or side. Signal and power wiring must be run in separate conduits.

C A U T I O N :

A two-wire circuit with separate phase and neutral conductors is required for

every branch circuit that will be connected to the dimmer rack. Shared neutral

circuit arrangements are not recommended for phase-control dimming systems

due to harmonics and potentially elevated neutral currents in a shared neutral

arrangement.
For retrofit installations where shared neutral circuits are already installed, or track

lighting installations where the track has a shared neutral, consult ETC Technical

Services for rack installation guidelines.
The Neutral of the supply to the dimming system should have at least the same

cross-sectional area as the phase conductors

N o t e :

Additional Sensor3 racks of the same size are

the single exception to the 15cm left clearance

rule. They can be installed side by side without

problems.

Senso

r

Senso

r

Figure 1: Sensor3 rack clearances

150mm

250mm

410mm