Ethernet network termination - rj45 connector, Panic circuit connections (optional), Panic circuit backplane connection – ETC Sensor3 CE (ESR3) Rack User Manual

Page 31

Advertising
background image

4

Control and Data Connections

23

Ethernet Network Termination - RJ45 Connector

Step 1:

Follow the directions provided in the Ethernet Termination Kit to terminate the

incoming CAT5 cable in the RJ45 UTP connector in the surface mounting box.

The kit is included with the dimmer rack door. Use the instructions provided with the kit for

proper Category 5 cable termination.
Step 2:

The surface mount box should be installed with the double-sided tape inside the

rack.

ESR3-36, ESR3-48: To the underside of the CEM3 backplane bracket.

ESR3-12, ESR3-24: To the bottom of the rack behind the backplane.

Step 3:

Use the provided male-to-male Ethernet patch cable to connect the surface

mounting box female RJ45 connector to the female RJ45 connector on the

CEM3 backplane.

Panic Circuit Connections (Optional)

Sensor3 racks can connect to an external Panic circuit if desired. Panic can be triggered by

a normally open or normally closed contact. The racks can also provide a feed to a lamp or

LED to indicate whether panic is active.

Panic Circuit backplane connection

Step 1:

Pull two 1.5mm

2

wires from your Panic contact location to the CEM3 backplane

through the data cable conduit or trunking. See

Running DMX Cable to Racks,

page 20

for data conduit installation details.

Step 2:

Connect the wires to the connector on the CEM3 backplane. Connect the Panic

contact input between “PANIC RTN” and “PANIC IN”.

Step 3:

Optionally, connect an external panic indication lamp between “PANIC OUT” and

“COM”. When panic is active, there will be a supply of +24VDC between “PANIC

OUT” and “COM”, with a maximum current draw of 25mA.

Step 4:

Set the switch on the backplane to indicate the contact type: Normally Open (NO)

or Normally Closed (NC).

Maintained

Closure

To trigger Panic,

use a

To external

indicators

(such as a

lamp or relay)

+24Vdc

(max 25mA

each)

To external

indicators

(such as a

lamp or relay)

+24Vdc

(max 25mA

each)

For Panic SEND/RTN:
NO - Normally Open closure
Disabled - Panic Disabled
NC - Normally Closed closure

To Sensor3
compatible

stations

SEND

Figure 25: Backplane Panic Connections