Sensor3 CE Rack (ESR3) Installation Manual

Dual Tracking Remote Select Switch connection (Optional)

If desired, a remote switch can be wired to the CEM3 backplane to control CEM3 selection

in racks equipped with ETC’s Redundant Tracking CEM3 option.

Step 1:

Pull 1.5mm

2

wires between your remote switch and the CEM3 backplane

through the data cable conduit. See

Running DMX Cable to Racks, page 20

for

data conduit installation details. For systems with no requirement for remote

tracking status indication three wires are required, otherwise four wires will be

required.

Step 2:

Connect the remote switch wires to the J12 connector on the rear of the

backplane.

Step 3:

Wire the remote switch and indicator to the J12 connector according to

Figure 26.

N o t e :

You must supply your own enclosed single-pole double-throw center-off switch to

install a remote select switch. You may optionally use an external 24V DC power

supply, or use the power supply from the rack backplane.

N o t e :

The J12 connector is a removable plug header and is easier to wire when it is

disconnected from the backplane in an installed rack.

1 2 3 4

+24Vdc COM

J12

Figure 26: J12 Dual Tracking remote connector wiring

Header at the top of the

backplane PCB

Orange remote tracking header.

Pin 1 is the pin closest to the phase

bars (left side of the rack as you look

in)

Position A - Primary

Position B - Secondary

An indicator lamp

50mA 24Vdc max for

internal power supply