9400 Technology applications | Table positioning

Parameter setting & configuration

Quick stop

30

L

EDS94TA10050xxxx EN 1.2 - 03/2010

5.8

Quick stop

[5-11] Basic function "Quick stop" (schematic diagram)

 The quick stop function can be activated as follows in the Lenze setting:

– By setting the digital input DI1 to LOW level.
– By a master control via the port LPortControl:

By setting bit 2 of the bit-coded control word 1.

 Parameter setting: Tab Application parameters  dialog level Overview All basic

functions Quick stop

The basic function "Quick stop" brakes the

drive to standstill within the deceleration

time set for the quick stop function after a

corresponding request independent of the

setpoint selection. The sequence control is

interrupted.
If the quick stop is deactivated, the drive

remains in standstill until the sequence

control is started again and takes over the

drive control.

LS_ManualJog

n

t

и

з

LS_Brake

n

t

LS_Limiter

n

t

LS_Quickstop

STOP

n

t

LS_Stop

internal
status machine

Status

machine

(basic drive

functions)

Basic drive functions

M

0

-100

100 200

LS_Homing

n

t

LS_Positioner

DI1

Parameter

Lenze setting

Value Unit

C00105

Quick stop deceleration time

0.000 s

C00106

Quick stop S-ramp time

0.00 %

C00107

Reference for quick stop deceleration time

Motor reference speed (C00011)

Control inputs of the function

Signal configuration

Lenze setting

Control input

(Multiplexer parameters)

DIGIN 1  Activate quick stop 1

C03135/1

Control word 1

bit 02

 Activate quick stop 2

C03135/2

FALSE  Activate quick stop 3

C03135/3