Configuring dnp3 – SATEC PM175 Manual User Manual

Page 108

Advertising
background image

‎Chapter 4 PAS Application Software

Configuring Communication Protocols

108

Series PM175 Powermeters

Initially these registers are reserved and none of them points
to an actual data register. To build your own Modbus register
map:

1. Select Protocol Setup from the Meter Setup menu and

click on the Modbus Registers tab.

2. Click on the Default button to cause the assignable

registers to reference the actual default meter register
11776 (0 through 119 are not allowable register

addresses for re-mapping).

3. Type in the actual addresses you want to read from or

write to via the assignable registers. Refer to the PM175
Modbus Reference Guide for a list of the available
registers. Notice that 32-bit Modbus registers should
always start at an even register address.

4. Click Send to download your setup to

the meter.

Configuring DNP3

DNP Options can be changed both via DNP3 and Modbus.
Refer to the PM175 DNP3 Reference guide for information on
the protocol implementation and a list of the available data

points.

DNP Options

To view or change the factory-set DNP options, select Protocol
Setup from the Meter Setup menu and click on the DNP
Options tab.