Analog inputs setup – SATEC PM175 Manual User Manual

Page 49

Advertising
background image

‎Chapter 3 Display Operations

Menu Operations

Series PM175 Powermeters

49

To exit the menu, press ESC.

The following table lists available setpoint options. For a list of
available setpoint triggers and actions, see

Using Control

Setpoints

in Chapter 4.

Label

Parameter

Options

Description

LGC.2-
LGC.4

Logical operator OR, AND

Combines setpoint triggers in a
logical expression

TrG.1-TrG.4 Trigger

parameter #1-

#4

See
Appendix C

The analog or digital value that is
used as an argument in a logical

expression

On.1-On.4

Operate limit

The threshold (in primary units) at
which the conditional expression

would be evaluated to true. Not
applicable for digital triggers.

OFF.1-

OFF.4

Release limit

The threshold (in primary units) at

which the conditional expression
would be evaluated to false. Defines

the hysteresis for analog triggers.
Not applicable for digital triggers.

Act.1-Act.4 Setpoint action

#1-#4

See
Appendix C

The action performed when the
setpoint expression is evaluated to

true (the setpoint is in operated
state)

On d

Operate delay

0-999.9 sec The time delay before operation

when the operate conditions are
fulfilled

OFF d

Release delay

0-999.9 sec The time delay before release when

the release conditions are fulfilled

Analog Inputs Setup

This entry appears only if the meter is ordered with optional
analog inputs. For more information on configuring analog

inputs in your meter, see

Programming Analog Inputs

in

Chapter 4.

To enter the menu, select the “A.In.1” or “A.In.2” entry from the
main menu for the AI1 and AI2 inputs respectively, and press
the ENTER button.

To change the analog input options:

1. Use the UP and DOWN arrow buttons to scroll to the

desired parameter.

2. Press the SELECT button to activate the lower window.
3. Use the UP and DOWN arrow buttons to adjust the

parameter value.

4. Press ENTER to confirm the new parameter setting, or

press ESC to discard changes.

5. You are returned to the middle window to select another

parameter, or store your new settings and exit the menu.


To store new settings and exit the menu:
1. When the middle window is highlighted, press the ENTER

button.

2. You return to the Main menu.

To exit the menu without saving your changes, press ESC.

The following table lists available analog input options.

SEtP

rEL.1

Act.1

SP.1

180

OFF.2

A.In.1

ESC

A.In.1

0

Lo

A.In.1

230

Hi

A.In.1

1

dEc.P

Advertising