‎Appendix A Technical Specifications

142

Series PM175 Powermeters

Communication Ports

COM1 (Optional modules)

Serial EIA RS-232 optically isolated port

Isolation: 2,000 V RMS
Connector type: DB9 female.
Baud rate: up to 115.2 kbps.
Supported protocols: Modbus RTU and Modbus ASCII, DNP3
(with firmware V25.2.01 and later).

RS-422/RS-485 optically isolated port

Isolation: 2,000 V RMS
Connector type: DB9 female.
Baud rate: up to 115.2 kbps.
Supported protocols: Modbus RTU and Modbus ASCII, DNP3
(with firmware V25.2.01 and later).

Ethernet Port

Transformer-isolated 10/100BaseT Ethernet port.
Connector type: RJ45 modular.
Supported protocols: Modbus/TCP on Port 502, DNP3/TCP on
Port 20000 (with firmware V25.2.01 and later).
Number of simultaneous connections: 4 (4 Modbus/TCP or 2
Modbus/TCP + 2 DNP3/TCP).

Dial-up Modem

Transformer-isolated internal 56K modem.
Connector type: RJ11.
Supported protocols: Modbus RTU and Modbus ASCII.

COM2

RS-422/RS-485 optically isolated port

Isolation: 2,000 V RMS
Connector type: removable, 5 pins.
Wire size: up to 14 AWG (up to 1.5 mm

2

).

Baud rate: up to 115.2 kbps.
Supported protocols: Modbus RTU and Modbus ASCII, DNP3
(with firmware V25.2.01 and later).

Real-time Clock

Accuracy: typical error 30 seconds per month @ 25

C

Log Memory

Onboard memory with battery backup: 1 Mbytes.

Display Module

Display: high-brightness seven-segment digital LEDs, two 4-
digit + one 6-digit windows
Keypad: 6 push buttons
Communication: EIA RS-485 port with 12V supply voltage
Connector type: DB15, 15 pins
Wires size: up to 14 AWG (up to 1.5 mm

2

)

Distance: up to 1000 m (3200 feet)