Using relay outputs – SATEC PM175 Manual User Manual

Page 69

Advertising
background image

‎Chapter 4 PAS Application Software

General Meter Setup

Series PM175 Powermeters

69

The available options are shown in the following table.

Parameter

Options

Default

Description

Pulse input mode PULSE MODE,

KYZ MODE

PULSE

MODE

In pulse mode, either leading, or

trailing edge of the input pulse is
recognized as an event. In KYZ

mode, both leading and trailing
edges of the input pulse are

recognized as separate events.

Pulse polarity

NORMAL (N.O.),
INVERTING (N.C.)

NORMAL

For the normal polarity, the open

to closed transition is considered a
pulse. For the inverting polarity,

the closed to open transition is
considered a pulse.
It has no meaning in KYZ mode
where both transitions are used.

Debounce time

1-1000 ms

10 ms

The amount of time while the state
of the digital input should not

change to be recognized as a new
state. Too low debounce time could

produce multiple events on the
input change.


The debounce time is used the same for both digital inputs. If
you change the debounce time for one digital input, the same
debounce time is automatically assigned to the other.

Using Relay Outputs

The PM175 is equipped with two relays. Each relay can be
operated either locally from the alarm/control setpoints in
response to an external event, or by a remote command sent
through communications, and can also be linked to an internal
pulse source to produce energy pulses.