‎Chapter 4 PAS Application Software

General Meter Setup

Series PM175 Powermeters

71

Parameter

Options

Default

Description

Retentive
mode

NO
YES

NO

Applicable for latched relays.
In non-retentive mode, the relay always

returns to its non-active state upon
power up.
In retentive mode, the relay status is

restored to what it was prior to loss of
power.

Pulse width 20-1000 ms

100 ms

The actual pulse width is a multiple of
the 1/2-cycle time rounded to the

nearest bigger value.
The pause time between pulses is equal
to the pulse width.

Pulse

source

NONE

kWh IMP
kWh EXP

kvarh IMP
kvarh EXP

kvarh TOT
kVAh

NONE

Links a pulse relay to the internal

energy pulse source. The relay must be
set into either pulse, or KYZ mode.

Pulse rate,
kWh/Pulse

0.1-1000.0

1.0 kWh/Pulse

Defines the pulse weight in kWh units
per pulse

Generating Energy Pulses through Relay
Outputs

To generate energy pulses through a relay output:

1. Set a relay to either pulse, or KYZ mode, and then select

a polarity (active pulse edge) for energy pulses and a
pulse width.

2. Select a source accumulator (type of energy) and the

pulse rate for your output.

3. Store your new setup to the device.

Programming Analog Inputs

The PM175 can be provided with two optional analog inputs
with options for 0-1mA, ±1mA, 0-20mA or 4-20mA input
currents, depending on the order. The 0-1mA and ±1mA
inputs can accept 100% overload currents, i.e., can actually

measure currents in the range of 0-2 mA and ±2mA.

The meter automatically converts the analog input readings
received from the analog-to-digital converter to the user-
defined engineering scale and shows the input values in true
engineering units, for example, in volts, amps, degrees, with
the desired resolution.

To configure the Analog Inputs in your device, select General
Setup from the Meter Setup menu, then click on the Analog

Inputs tab. If you are programming your device online, analog
inputs are designated as not available if they are not present in
the device.