En50160 evaluation and recording, En50160 background, Compliance limits – SATEC PM175 Manual User Manual

Page 94: Indicatives values

Advertising
background image

‎Chapter 4 PAS Application Software

EN50160 Evaluation and Recording

94

Series PM175 Powermeters

EN50160 Evaluation and Recording

EN50160 Background

The EN50160 European standard “Voltage characteristics of
electricity supplied by public distribution systems” issued by
CENELEC defines the main physical characteristics of electric
energy supplied by low and medium voltage public distribution
systems under normal operating conditions.

The voltage characteristics are evaluated using a statistical
approach. The standard and its referenced publications
specify for each voltage characteristic:

-

Method of evaluation

-

Integrating interval for a single measurement

-

Observation period

-

Statistical indication of the probability of not exceeding a specified limit

-

Standard compliance limits or indicative values within which any
customer can expect the voltage characteristics to remain

Compliance Limits

For some voltage characteristics, the standard provides

definite limits that can be complied with for most of the time
considering the possibility of relatively rare excursions beyond
these limits. Limits are set with a view to compliance for a
percentage of the observation time, e.g. 95% of the
observations in any period of one week.

The following table gives the characteristics for which definite
limits have been specified by the standard.

Indicatives Values

For the remaining characteristics of the voltage, by their
unpredictable nature, the standard gives only indicative
values, which are intended to provide users with information
on the order of magnitude which can be expected.

The following table gives the characteristics for which
indicative values have been specified by the standard.

Voltage

Characteristic

Indicative

values

Observation

period

Voltage dips

Less than 1

s, 60%
depth

Year

Short
interruptions

70% less
than 1 s

Year

Long

10 to 50%

Year

Voltage characteristic

Compliance with stated

limits, % of time

Observation

period

Power frequency

1% for 95% of a week

1% for 99.5% of a year

+4/-6% for 100% of time

Week, year

Voltage variations (supply
voltage magnitude)

10% Un for 95% of time

Week

Rapid voltage changes

4-5% Un (up to 10% Un)

Day

Flicker (fluctuations of
voltage magnitude)

Plt

1 for 95% of time

Week

Voltage unbalance

2-3% for 95% of time

Week

Harmonic voltage

THD

8 for 95% of time

Week

Interharmonic voltage

To be defined

Week

Mains signaling voltage

Within “Meister-curve” for

99% of time

Day