Configuring the event recorder, Configuring the data recorder, Conventional data log files – SATEC PM175 Manual User Manual

Page 88

Advertising
background image

‎Chapter 4 PAS Application Software

Configuring Recorders

88

Series PM175 Powermeters

No.

File

Type

Size,

Bytes

Channels Number of

Records

Number of

Events

Description

11

Data log #10

Wrap
around

7920

3

12

12

Configured for
EN50160 harmonics

survey

18

Waveform log #1 Wrap

around

256320 6

40

20

32 samples/cycle
x 32 cycles/series

19

Waveform log #2 Wrap

around

256320 6

40

20

128 samples/cycle
x 8 cycles/series

27

EN50160 Power
Quality log

Wrap
around

32000

1000

1000

Configuring the Event Recorder

To configure the Event log file:

1. Double click on the Event Log file partition with the left

mouse button.

2. Select a partition type for your file.
3. Select the maximum number of records you want to be

recorded in the file.

4. Click OK, then send your new setup to the meter or save

to the device database.

By default, the Event recorder stores all events related to
configuration changes, reset, and device diagnostics. In

addition, it records events related to setpoint operations. Each
setpoint should be individually enabled for recording to the
Event log.

To log setpoint operations, add the “Event log” action to the
setpoint actions list. When a setpoint event happens, the
Event recorder logs all setpoint conditions that caused the
event and all setpoint actions performed in response to the
event. Logging actions themselves will not be recorded to the
Event log.

Configuring the Data Recorder

The Data recorder is programmable to record up to 16 data
parameters per record in each of 16 data log files. The list of

parameters to be recorded to a data log is configured
individually for each file.

Conventional Data Log Files

To create a new data log file or re-configure an existing file:

Advertising