Network address, Counters setup – SATEC PM175 Manual User Manual

Page 47

Advertising
background image

‎Chapter 3 Display Operations

Menu Operations

Series PM175 Powermeters

47

Label

Parameter

Options

Default

Description

Addr

Device address Modbus: 1-247

DNP3: 0–65532

1

Device network address

bAud

Baud rate

300-115200 bps

19200 bps The port baud rate

dAtA

Data format and
parity

7E, 8N, 8E

8N

7E data format should
not be used with the
Modbus RTU and DNP3

protocols

Network Address

This menu allows you to configure the device IP address and
the default gateway address for the Ethernet port. To enter the
menu, select “nEt” from the main menu, and then press the
ENTER button.

To change the IP Address and Default Gateway:

1. To change the device IP address, select the “A” entry in

the upper window with the UP and DOWN arrow buttons.
To change the default gateway address, select the “G”
entry.

2. Press the SELECT button to activate the first address

digit.

3. Use the UP and DOWN arrow buttons to adjust the digit.
4. Press the SELECT button to advance to the next digit.
5. Adjust the remaining address digits.
6. Press ENTER to confirm your new setting, or press ESC

to discard changes.

To exit the menu, press ESC.

Counters Setup

The PM175 has four six-digit counters that can count pulses
delivered through the device digital inputs with a
programmable scale factor, or events that trigger setpoint

operations. This menu allows you to link digital inputs to the
counters and define a pulse multiplier for each counter. To
enter the menu, select the “Cnt” entry from the main menu and
press the ENTER button.

The menu uses three entries:
1. The upper window indicates a counter number.
2. The middle window selects a digital input to be linked to

the counter.

3. The lower window defines a counter multiplier.


Use the UP and DOWN arrow buttons to scroll to the desired
counter.

To change the counter options:

1. Press the SELECT button to activate the middle window.
2. Use the UP and DOWN arrow buttons to link a digital

input to the counter or to disable the counter input.

3. Press the SELECT button to activate the lower window.
4. Use the UP and DOWN arrow buttons to enter the desired

multiplier.

5. Press ENTER to confirm your changes and to store the

new settings, or press ESC to discard changes.

Cnt.1

1

Inp.1

A.

192.

000.203

168.

G.

192.

000.001

168.