Setting up the ethernet – SATEC PM175 Manual User Manual

Page 62

Advertising
background image

‎Chapter 4 PAS Application Software

Configuring Communications in your Meter

62

Series PM175 Powermeters

To change the port settings in your meter, select desired port
parameters, and then click Send. For the available
communication options, see

Communication Ports

in Chapter

3.

NOTES

1. In meters with the Ethernet option, the device provides the

permanent Modbus TCP server on port 502. Selecting
the DNP3 protocol on the Ethernet port launches the
DNP3 TCP server in addition to the Modbus server
allowing simultaneous connections on both ports.
Selecting the Modbus protocol disables the DNP3 TCP
server.

2. When you change the COM1 settings through the

Ethernet port, the device port restarts so communications
will be temporarily lost. You may need to wait some
additional time until PAS restores a connection with your
device.

Setting Up the Ethernet

To enter the Setup dialog, select the device site from the list
box on the PAS toolbar, select Communications Setup from
the Meter Setup menu, and then click on the Network Setup
tab.

Advertising