Factory preset periodic data logs, Tou profile data log files – SATEC PM175 Manual User Manual

Page 90

Advertising
background image

‎Chapter 4 PAS Application Software

Configuring Recorders

90

Series PM175 Powermeters

automatically update the “Parameter” box with the
following parameter in the group.

8. Add the name for your data log file in the “Name” box. It

will appear in the data log reports.

9. Save your new setup to the device database, and send it

to the meter.

Factory Preset Periodic Data Logs

Data logs #1 and #2 are factory preset for periodic recording of
the standard power quantities as shown in the following table.

No.

Parameter

No.

Parameter

Data Log #1

1

V1/V12

9

Total kVA

2

V2/V23

10

Total PF

3

V3/V31

11

V1/V12 THD

4

I1

12

V2/V23 THD

5

I2

13

V3/V31 THD

6

I3

14

I1 THD

7

Total kW

15

I2 THD

8

Total kvar

16

I3 THD

Data Log #2

1

V1/V12 Demand

9

KVA Sliding Demand

2

V2/V23 Demand

10

kWh Import

3

V3/V31 Demand

11

kWh Export

4

I1 Demand

12

kvarh Import

5

I2 Demand

13

kvarh Export

6

I3 Demand

14

kVAh

7

kW Import Sliding Demand

15

In

8

kvar Import Sliding Demand

16

Frequency

TOU Profile Data Log Files

Data log #16 is configurable to store TOU daily profile log
records on a daily basis.

A TOU profile log file is organized as a multi-section file that
has a separate section for each TOU energy and maximum

demand register. The number of sections is taken automatically
from the Summary/TOU Registers setup (see

Setting up Total and

Tariff Registers

). If you selected to profile TOU maximum

demands along with energy registers, then the number of
sections in the file will be twice the number of the allocated
TOU registers.

To configure a TOU daily profile log file:

1. Configure your TOU registers and TOU schedule in the

meter before allocating memory for the profile log file (see

Setting up Total and Tariff Registers

).

2. Double click on the Data Log#16 partition with the left

mouse button.