‎Chapter 4 PAS Application Software

General Meter Setup

66

Series PM175 Powermeters

The following table lists available device options.

Parameter

Options

Default

Description

Power Calculation
Mode

S=f(P, Q) (using
reactive power),
Q=f(S, P) (using
non-active power)

S=f(P, Q)

The method used for calculating
reactive and apparent powers

(see “Power Calculation Modes”

below)

Energy Roll Value 1000.0 kWh

10000.0 kWh
100000.0 kWh
1000000.0 kWh
10000000.0 kWh
100000000.0 kWh

100000000.0 The value at which energy

counters roll over to zero

Phase Energy
Calculation

Disabled, Enabled

Disabled

Enables phase energy calculations

Analog Expander
Option

1

Disabled
0-20 mA

4-20 mA
0-1 mA

±1 mA

Disabled

Enables outputs for the AX-8
analog expanders through port

COM2. See “Programming the
Analog Expander”

Backup Battery

OFF = switched OFF
On = switched ON

OFF

Allows to conserve a battery while
the meter is out of operation

Energy Test Mode OFF = disabled

Wh pulses

varh pulses

Disabled

Setting this option puts the meter
into the energy test mode

Volts Scale, V

10-828 V

144 V

The maximum voltage scale
allowed, in secondary volts. See

Data Scales

in Appendix F

Amps Scale, A

2

nominal CT

secondary current
(2A, 10A)

2A/10 A

The maximum current scale
allowed, in secondary amps. Not
changeable. See

Data Scales

in

Appendix F

1

Do not enable the analog expander output if you do not have the

analog expander connected to the meter, otherwise it will disturb the

computer communications.