‎Appendix G Device Diagnostic Codes

168

Series PM175 Powermeters

Appendix G Device Diagnostic Codes

Diagnostic

Code

Description

Reason

2

Memory/Data fault

Hardware failure

3

Hardware watchdog reset

Hardware failure

5

CPU exception

Hardware failure

6

Run-time software error

Hardware failure

7

Software watchdog

timeout

Hardware failure

8

Power Down/Up

Normal power-up sequence

9

Warm restart

External restart via communications or
by firmware upgrade

10

Configuration reset

Corrupted setup data has been

replaced with the default configuration

11

RTC fault

The clock time has been lost

13

Low battery

Battery replacement is required. With
auto-reset.

15

EEPROM fault

Hardware failure


See

Device Diagnostics

in Chapter 4 for more information on

the PM175 built-in diagnostics.